Notes:
4680 SQ FT, CALT / REPUBLIC TITLE OF TEXAS
6/20/2007 12:00:00 AM
1. floor mounted mop sink req'd. and floor drain at secondary restrooms.
2. fully sprinkled per initial CIFO.
3. any wood used shall be fire treated.
4. interior finishes: class C
flame spread index---76---200
smoke developed length 0---450
5. tempered glass where req'd.
6. clarify where roof access is located.
7. 2806 sq.ft. of open office space, no vestibule req'd.
Mechanical ordinance 06-11-113
*All duct work to be sealed with mastic, welds, or gaskets; Tapes not accepted.
*All exhaust fans to terminate outside of the bldg.
*Fresh air intakes to be 10 ft. away or 2 ft. below exhaust gas openings & require dampers to close intake when not in use.
*Mech. Contractor to be responsible for duct sizing and load calculation.
*Mech. Contractor to verify fresh air intake per IMC 403 & table 403.3
*Mech. Installation to comply with 2003 IECC and supplements.
*Rigid duct required with 6 ft. (R-6) flex duct connector allowed between rigid duct and diffuser.
*Set back T-Stats required for each zone.
*Smoke detectors/dampers to be installed per chapter 6 of IMC.
*Subject to field review and inspection
plumbing notes in trak-it and on plans