Notes:
SPCL EVENT / FRISCO SUNRISE ROTARY 5K RUN TENT
3/7/2011 12:00:00 AM
Geoffrey Davis
Re: Submittal for a Temporary Tent Structure (60x60) for Frisco Sunrise Rotary, located at 6101 Frisco Square. Event date March 19th.
We have received and reviewed the proposed site location and documentation for a temporary tent structure in accordance with ordinances adopted by the City of Frisco. The location and use were found acceptable subject to the following comments.
1. An inspection from the Fire Marshal’s Office and the Building Department is required prior to occupancy.
2. Tent cannot obstruct the fire lane or vehicular traffic flow.
3. Need to post the occupant load sign – The Occupant Load can be obtained from the Building Department.
4. Need to provide (3) exits spaced at equal intervals around the perimeter of the tent. Minimum width of each exit is 72 inches wide. Exit openings must comply with the 2006 IFC Chapter 24. Aisle widths and exits shall be maintained per the 2006 IFC and IBC.
5. Illuminated exit signs and shall be provided over each required exit.
6. The means of egress shall be illuminated with light having an intensity of not less than 1 foot candle at the floor level while the structure is occupied. The means of egress illumination fixtures shall be supplied from a separate circuit or source of power.
7. Two sources of power shall be provided.
a. One source of power must be from an approved emergency system.
b. System must be installed in accordance with the ICC Electrical Code.
c. If supplied, the generator will need to be placed a minimum of 20 ft from tent.
8. Need to provide (3) 2A10BC “ABC” fire extinguisher.
a. The fire extinguisher must have a current inspection tag.
b. The fire extinguisher shall be placed in the path of egress and mounted so that its top is not more than 5 feet above the floor.