CHRISTIE RANCH AMENITY CENTER POOL
5/31/2007 12:00:00 AM
- POOL BARRIER INCLUDING ALL ENTRIES/EXITS MUST MEET STATE MINIMUM STANDARDS. SPACING IN FENCE NOT EXCEED 4 INCHES. GATES MUST SWING AWAY FROM POOL AREA, BE SELF CLOSING/LATCHING, AND BE LOCKABLE. NO GAPS >1/2" WITHIN 18" OF THE LATCHING MECHANISM. BARRIER MAY NOT HAVE CLIMB HAZARDS AND CLIMB HAZARDS MAY NOT EXIST WITHIN 3 FT OF ANY PART OF BARRIER.
- RESTROOM LAVATORIES AND SHOWER MUST HAVE HOT WATER AND DRAIN TO SANITARY SEWER.
- PROVIDE AND LOCATE WATER DRINKING FOUNTAINS.
- EQUIPMENT ROOM MUST HAVE ADEQUATE VENTILATION - LOUVERED OR MECHANICAL - AND HAVE LOCKABLE ACCESS.
- ALL LEADING EDGES OF BENCHES, STEPS AND LEDGES REQUIRE 1 INCH MINIMUM TILE STRIPE.
- LIGHTS MUST BE PROTECTED BY GFCI. EQUIPMENT ELECTRICAL DISCONNECT MUST BE VISIBLE INSIDE POOL EQUIPMENT ROOM.
- CHAIRLIFT SLEEVE (MUST BE WITHIN 24 INCHES OF WATER'S EDGE).
- TWO SETS OF SAFETY EQUIPMENT ARE REQUIRED ON POOLS OVER 2000 SQ FT OF SURFACE AREA.
- AUTOFILL LINE, IF PROVIDED, MUST NOT PROTRUDE BEYOND COPING EDGE.
- PROVIDE AND LOCATE KNOX BOX LOCATED OUTSIDE OF POOL BARRIER. - PROVIDE AND LOCATE EMERGENCY 911 PHONE OUTSIDE OF POOL BARRIER.
- MENS AND WOMENS REST ROOMS REQUIRE BABY CHANGING STATIONS. - DEPTH MARKERS AND "NO DIVING AND INTERNATIONAL SYMBOL MUST BE PROVIDED MINIMUM OF EVERY 25 FT. DEPTH MARKERS MUST MEET OTHER APPLICABLE STANDARDS.
- ENTRY/EXITS MUST BE PROVIDED EVERY 75 FT. OF POOL WALL LENGTH OR FRACTION OF AND BE INSTALLED ACCORDING TO STATE MINIMUM STANDARDS.
- SKIMMER EQUALIZER LINES ARE NOT ALLOWED.
- ENGINEERS LETTERS ON FILE.