Notes:
1. APPLICABLE CODES SHALL BE THE 2003 IBC, IPC, IMC, IECC, IFGC AND IFC.
2. SINCE THE ARCHITECTURAL SITE PLAN DOESN'T SHOW DUMPSTER, PROVIDE PLANNING FOR DUMPSTER ENCLOSURE FACILITY & TRUCK ROUTE WITH MIN. 20'-RADIUS AT ALL TURNS, UNLESS THE FACILITY IS LOCATED WITH GATES FACING 30 DEGREES MAX. OFFSET ANGLE FROM A FIRELANE. SYSTEM MUST BE INDICATED ON SITE PLAN AS BASIC REQUIREMENT AND DETAILED AS PER STANDARD CRITERIA, REGARDLESS OF ANY SPECIAL TRASH SERVICE ARRANGEMENT, WHICH MUST BE DECLARED BY A LETTER AND CONDITIONALLY APPROVED IN WRITING BY THE ENVIRONMENTAL SERVICES DEPARTMENT (972-292-5900) PRIOR STARTING ANY CONSTRUCTION. TOTAL OR PARTIAL DISPENSATION (WITH ONLY ONE DUMPSTER FOR THE PERISHABLE WASTE), MAY BE ALLOWED TEMPORARILY AS SUITABLE TO CITY OFFICIALS.
3. ROOFS THAT SLOPED TO DRAIN OVER THE ROOF EDGES SHALL BE PROVIDED WITH ROOF GUTTER WITH DOWNSPOUTS THAT DISCHARGE INTO SITE STORM DRAINAGE SYSTEM.
4. WOOD TRIM, BOARD AND BATTEN ARE NOT ALOWED IN EXTERIOR FACADES OF THE BUILDING AS PER CITY OF FRISCO ZONING ORDINANCE, 100% MASONRY REQUIRED.
5. UNIT HEATERS SHALL BE PROVIDED IN THE EQUIPMENT AND TOILET ROOMS, WALLS AND CEILING SHALL BE INSULATED TO PROTECT PLUMBING PIPES FROM FREEZING.
6. STRUCTURAL PLANS SHALL BE DESIGN BASED ON THE 2003 IBC NOT THE 2003 IRC. SUBMIT ADDENDUM FOR THESE STRUCTURAL PLANS.
7. HI/LO DRINKING FOUNTAIN REQUIRED.
8. STORAGE/EQUIPMENT ROOM IS AN INCIDENTAL AREA FROM THE MAIN AREA THEREFORE SHALL BE SEPARATED BY AT LEAST 1-HOUR FIRE RATED WALL CONSTRUCTION FROM THE FLOOR TO ROOF DECK ABOVE.
9. SILL PLATES AND POST/COLUMNS SHALL BE OF PRESERVATIVE TREATED WOOD.
10. CONTINGENT UPON P+Z & CIVIL ENGG APPROVALS OF FINAL SITE PLAN, COMPLIANCE TO BLDG CODE & LOCAL REQUIREMENTS, PERTINENT LEGISLATIONS AND REVIEW COMMENTS.
11. SUBJECT TO ADDITIONAL REQUIREMENTS FROM HEALTH DEPT & M.E.P. REVIEWS, FIRE MARSHAL AND FIELD INSPECTIONS.
1216 SQ FT, CNEW / CHRISTIE RANCH AMENITY CENTER