Permit Info
Short Description:
vacant ??NOTE? 2141 SQ FT, CIFO /
Expiration Date:
6/16/2004
Notes:
1- CONTINGENT UPON FULL COMPLIANCE WITH ALL CITY COMMENTS, CODE REQUIREMENTS AND PERTINENT LEGISLATIONS.
2- CONFORM TO ASBESTOS SURVEY REQUIREMENTS BEFORE ALTERING ANY PART OF EXISTING CONSTRUCTION.
3- SUBMITTAL OF MEDICAL PHYSICIST'S REPORT IS REQUIRED BEFORE CONSTRUCTION OF X-RAY EQUIPMENT AREAS.
4- USE OF MEDICAL GASES FOR SURGERY IS PROHIBITED UNDER THIS PERMIT SINCE NO PROVISION OF VENTED AND FIRE RATED STORAGE, AS REQUIRED BY NFPA 99, IS SHOWN ON THE SUBMITTED PLANS.
5- PLUMBING ALONG THE DEMISING WALLS MUST BE PLACED IN FURR-OUT SPACES, OUTSIDE THE ENTIRE DEMISING WALL, NOT TO INTERFERE WITH THE REQUIRED 1-HR FIRE RATED INTEGRITY AS PER UL-U465.
6- PROVIDE HI/LO DRINKING FOUNTAIN AS REQUIRED.
7- SUBJECT TO M.E.P. REVIEWS, FIRE MARSHAL AND FIELD INSPECTIONS.
vacant ??NOTE? 2141 SQ FT, CIFO /
Parcel Info
City/State/Zip:
FRISCO, TX,
Subdivision:
LEGACY CENTER
|
OWNER | KENT JULIUS DMV | (972)377-8467 | | 4509 BALLYMENA | FRISCO, TX 75034 |
MAIL TO | KENT JULIUS DMV | (972)377-8467 | | 4509 BALLYMENA | FRISCO, TX 75034 |
APPLICANT | TRI-STAR CONST., INC | (972)221-5558 | | 220 ELM ST SUITE 100 | LEWISVILLE, TX |
CONTRACTOR | TRI-STAR CONST., INC | (972)221-5558 | | 220 ELM ST SUITE 100 | LEWISVILLE, TX |
ELECT. CTR. | HUMPHREY & ASSOCIATES, INC. | (972)620-1075 | | 11235 SHADY TRAIL | DALLAS, TX 75229 |
GEN. CONTR. | TRI-STAR CONST., INC | (972)221-5558 | | 220 ELM ST SUITE 100 | LEWISVILLE, TX |
MECH. CTR. | ADVENT A/C X-01/03 | (972)221-4373 | | 500 S KEALY | LEWISVILLE, TX 75067 |
PLUMBING | ALAN'S PLUMBING CO. X-10/03 | (817)626-2526 | | POB 162341 | FORTH WORTH, TX 76161 |
Total Fees |
Charged: $0.00
Balance Due: $0.00
|
|
BACKFLOW | APPROVED |
6/16/2003
| | 6/16/2003 | |