Notes:
1- CONTINGENT UPON FULL COMPLIANCE WITH ALL CITY COMMENTS, CODE REQUIREMENTS AND PERTINENT LEGISLATIONS.
2- CONFORM TO ASBESTOS SURVEY REQUIREMENTS BEFORE ALTERING ANY PART OF EXISTING CONSTRUCTION.
3- SUBMITTAL OF MEDICAL PHYSICIST'S REPORT IS REQUIRED BEFORE CONSTRUCTION OF X-RAY EQUIPMENT AREAS.
4- USE OF MEDICAL GASES FOR SURGERY IS PROHIBITED UNDER THIS PERMIT SINCE NO PROVISION OF VENTED AND FIRE RATED STORAGE, AS REQUIRED BY NFPA 99, IS SHOWN ON THE SUBMITTED PLANS.
5- PLUMBING ALONG THE DEMISING WALLS MUST BE PLACED IN FURR-OUT SPACES, OUTSIDE THE ENTIRE DEMISING WALL, NOT TO INTERFERE WITH THE REQUIRED 1-HR FIRE RATED INTEGRITY AS PER UL-U465.
6- PROVIDE HI/LO DRINKING FOUNTAIN AS REQUIRED.
7- SUBJECT TO M.E.P. REVIEWS, FIRE MARSHAL AND FIELD INSPECTIONS.
2141 SQ FT, CIFO / LEGACY VETERINARY CENTRE