Notes:
1- CONTINGENT UPON P+Z & CIVIL ENGG APPROVALS OF FINAL SITE PLAN, COMPLIANCE TO BLDG CODE & LOCAL REQUIREMENTS, PERTINENT LEGISLATIONS AND REVIEW COMMENTS.
2- PENDING SUBMITTAL OF REVISED TRASH FACILITY ORIENTED POSITION AND DETAILS AS PER CITY CRITERIA. DESIGN APPROVAL MUST BE ALSO CONFIRMED BY THE ENVIRONM'L SVCS DEPT (972-335-5519) PRIOR STARTING ANY CONSTRUCTION.
3- ADD TWO PARK'G SPACES (MADE POSSIBLE BY THE RELOCATED TRASH FACILITY) FOLLOWING SUGGESTED SOLUTION MARKED ON DWG C1, UNLESS A DIFFERENT ARCHITECT'S PROPOSAL IS SUBMITTED AND APPROVED AS REQ'D.
4- CONC. PAVING THICKNESS IN DUMPSTER ENCLOSURE AREA AND MIN. 40' FEET TRUCK APPROACH IN FRONT OF GATES MUST BE MIN. 7" AS REQ'D.
5- STRUCT'L ENGR TO RECHECK BLDG'S STRUCT'L CALCULATIONS FOR REQ'D EXPOSURE 'C' & SUBMIT REPORT IF ANY ADJUSTMENTS ARE NECESSARY OR NOT.
6- STOREFRONT GLAZING IS NOT APPROVED UNLESS DOCUMENTED WITH MAX. SHGC=0.6 IN CASE OF UNSHADED GLASS AND MAX. 0.7 FOR SHADED GLASS (WHICH FOR CLEAR GLASS MIGHT NEED TO BE DOUBLE PANE). PRODUCT'S MANUF. DOCUMENTATION MUST BE SUBMITTED FOR VERIFICATION & APPROVAL PRIOR INSTALLATION.
7- BLDG ENVELOPE INSULATION IS PART OF SHELL PERMIT. IF WALL INSULATION AT EXTERIOR WALLS IS LEFT TO FINISH-OUT CONTRACTORS, A WARNING SIGN MUST BE POSTED AT EACH TILTWALL PANEL THAT A MIN. OF R-11 BATT INSULATION MUST BE INSTALLED BEFORE FINISH IS APPLIED.
8- SUBJECT TO MODIFICATIONS FOLLOWING APPROVALS OF FINISH-OUT PLANS.
9- SUBJECT TO M.E.P. REVIEWS, FIRE MARSHAL AND FIELD INSPECTIONS.
17500 SQ FT, CNEW / 121 / PRESTON RETAIL CENTER