Notes:
1. DOOR 107------ NEED DETAILS ON THIS DOOR @ JANITOR'S CLOSET.
2. STEAM ROOMS------SUBMIT RM. DETAILS SHOWING HANDICAP ACCESSIBILITY & TURN AROUND AS REQ'D.
3. STEAM SHOWER------SHOW CURTAIN HERE FOR ACCESSIBILITY INSTEAD OF DOOR.
4. AREA 118------- NEED ENGINEERS DETAILS ON REINFORCING WHERE THIS DOOR WAS CUT IN.
9-08-05 jm)
these issues have been corrected
1. janitor closet --no door curtain will be installed
2. steam rooms have a 5' turnaround space and no benches
3. steam shower ste. 113 has been enlarged to allow for door
4. relaxation area 118 shows an exterior door that was part of the original bldg. shell. This door was engineered in the shop dwgs. for the tilt wall.
5. subject to field approval
6. fully sprinklered.
7. add correct hi/lo drinking fountains----SEE NOTE AT BOTTOM
8. 1 hr. walls at storage rm. with 45 min. doors.
OWNER CAME IN ON 9-23-05 GILBERT, JEFF M. AND OWNER AGREED THAT THE ISSUE OF PROVIDING BOTTLED WATER FOR THE PATRONS BY MEANS OF A GLASS FRONT REFRIGERATOR MET THE CONTENT OF THE CODE.
NO HI/LO DRINKING FOUNTAIN REQUIRED.
1. MINIMUM #12 COPPER CONDUCTORS PERMITTED EXCEPT FOR CONTROLS.
2. NO ALUMINIM WIRE PERMITTED.
3. PULL EQUIPMENT GROUNDS IN ALL RACEWAYS.
4. PROVIDE EXIT AND EMERGENCY LIGHTING AS NOTED AND REQUIRED PER 2000 IBC.
5. LIGHTING AND CONTROLS SHALLCOMPLY WITH 2000 IECC WHEREAPPLICABLE.
ALL ELECTRICAL INSTALLATIONS WILL
BE SUBJECT TO FIELD INSPECTIONS
AND INSPECTOR APPROVALS.
ELECTRICAL WILL BE DESIGNED AND
INSTALLED PER THE 1999 NATIONAL
ELECTRICAL CODE WITH LOCAL AMENDMENTS
STATED IN CITY OF FRISCO ORDINANCE 00-03-02
ALONG WITH THE FOLLOWING COMMENTS.