Notes:
1- CONTINGENT UPON COMPLIANCE WITH P+Z & CIVIL ENGINEERING APPROVALS OF FINAL SITE PLAN, BLDG CODE & LOCAL REQUIREMENTS, PERTINENT LEGISLATIONS AND REVIEW COMMENTS.
2- PROVIDE DUMPSTER ENCLOSURES FOLLOWING THE CITY'S STANDARD CRITERIA AS REQ'D. THE OVERALL SYSTEM MUST BE APPROVED BY THE ENVIRONM'L SVCS DEPT (972-335-5519) PRIOR STARTING ANY CONSTRUCTION.
3- HEIGHT OF PARAPETS SHALL BE THE COMBINATION OF TOTAL SCREENING OF MECH'L EQUIPMENT, SAFETY GUARD/DISTANCE FROM THE ROOF EDGE (Sec. 1003.2.12.4) AND THE MINIMUM OF 2'-6" ABOVE FINISHED ROOFING (Sec. 704.11.1) AS REQ'D.
4- PROVIDE ENCLOSED ENTRANCE VESTIBULES AS PER ENERGY CODE.
5- ALL EXTERIOR AND/OR INTERIOR GLAZING ASSEMBLIES MUST CONFORM TO IMPACT & LOADS RESISTANCES, ENERGY AND SAFETY GLASS REQUIREMENTS FOR SPECIFIC USE AND LOCATION.
6- POOL, SPA AND JUICE BAR RELATED AREAS ARE SUBJECT TO SPECIFIC APPROVALS FROM THE HEALTH DEPT.
7- SUBJECT TO M.E.P. REVIEWS, FIRE MARSHAL AND FIELD INSPECTIONS.
(1/19/2005 09:41 JS) (1/19/2005 09:04 JS)
PLEASE COMPLY WITH HEALTH ORDINANCE # 00-03-19 AND SMOKING ORDINANCE #00-12-12.
(1/19/2005 09:04 JS)A011- POOL PLANS MUST BE SUBMITTED SEPARATELY AND MUST COMPLY WITH #02-12-138. HEALTH AND FOOD SAFETY WILL DO A HEALTH FINAL PRIOR OT C.O. AND WILL DO THE PRE-PLASTER AND POOL FINAL INSPECTIONS IN POOL AREA. SEE FINISH NOTES ID-8.; E 5.0 -ADD ONE HAND SINK. ADD ONE SINGLE-COMPARTMENT SINK FOR FOOD PREP, IF DONE. FOOD SERVICE LIMITED TO JUICE DRINKS AND SMOOTHIES UNLESS GREASE INTERCEPTOR IS PROVIDED AND SIZED APPROPRIATELY.
(1/19/2005 10:11 MBW) ALL SUBCONTRACTORS MUST VALIDATE AND OBTAIN CURRENT REGISTRATION WITH THE CITY PRIOR TO START OF PROJECT.
45000 SQ FT, CNEW / LA FITNESS