Notes:
3/20/2018 7:04:20 PM
PERMIT IS FOR TENT SITE FOR BEST BUDDIES EVENT IN SIMPSON PLAZA.
PERMIT DOES NOT AUTHORIZE EVENT OR MISC. STRUCTURES.
MAY NOT OBSTRUCT FIRE LANE, HANDICAP PARKING & ACCESSIBILITY, MANDATORY PARKING, STREET TRAFFIC, RIGHT OF WAY, OR VISIBILITY(VAM).
MAY MOUNT ONE BANNER NOT TO EXCEED 48 SQ FT TO TENT WITHOUT ADDITIONAL PERMIT.
ALL AIRBORNE DEVICES (FLAGS, PENNANTS, BALLOONS, ETC.) ARE PROHIBITIED PER ORDINANCE 16-03-25.
SMOKING PROHIBITTED IN ENCLOSED SPACES. REGULATED PER ORDINANCE #06-11-18.
ANY/ALL FOOD PROVISIONS MUST BE APPROVED BY THE HEALTH AND FOOD SAFETY DEPARTMENT UNDER SEPERATE TEMPORARY HEALTH PERMIT.
SUBJECT TO APPROVAL BY FIRE MARSHAL AND POLICE DEPARTMENT.
PERMIT VALID 04/07/2018
CALL FIRE MARSHAL OFFICE FOR TENT INSPECTION AT LEAST ONE WORKING DAY IN ADVANCE AT 972-292-6328.
TWO 20X20 FT AND SEVERAL 10X10 FT TENTS.
1. An inspection from the Fire Marshal’s Office and the Building Department is required prior to occupancy. Need to call the Fire Marshal’s Office at 972-292-6328, when the tent, stage, and equipment are set and ready for inspection.
2. The equipment, tent, and stage cannot obstruct the fire lane or vehicular traffic flow.
3. Need to post the occupant load sign for the following tent structures:
a. 10x10 = Max 7 people per tent.
b. 20x20 = Max 26 people per tent.
4. If sides are installed, (2) exits will need to be provided. The exits must be spaced at equal intervals around the perimeter of each the tent. Minimum width of each exit is 72 inches wide. Exit openings must comply with the 2015 IFC Chapter 24. Aisle widths and exits shall be maintained per the 2015 IFC and IBC.
a. If sides are installed, exit signs shall be provided over each required exit.
5. The generator will need to be placed a minimum of 20 ft from tent.
a. The generator and associated wiring must be inspected by the cities electrical inspector. Wiring shall not create a tripping hazard.
6. Need to provide (1) 2A10BC “ABC” fire extinguisher for each 20x20 tent, and additional fire extinguishers will need to be spaced throughout the 10x10 tent area.
a. The fire extinguisher must have a current inspection tag.
b. The fire extinguisher shall be placed in the path of egress and mounted so that its top is not more than 5 feet above the floor.
7. Need to provide and post a “NO SMOKING” sign at each tent location, including bounce house location.
8. Smoking, open flames or cooking is not permitted under tent structures or bounce house location.
9. If permitted, cooking operations that produce sparks or grease-laden vapors shall not be performed within 20 feet of the tent or bounce house structure.
10. Must meet all the minimum requirements of the International Fire Code and Building Code.
11. Additional requirements may be required when a site inspection is conducted.