Notes:
SPCL EVENT / KROGER TENT (seasonal sale-mothers day)
4/29/2010 12:00:00 AM
PERMIT IS FOR TENT ONLY AND DOES NOT AUTHORIZE EVENT OR MISC. STRUCTURES. MAY NOT OBSTRUCT FIRE LANE, HANDICAP ACCESS, MANDATORY PARKING, STREET TRAFFIC, RIGHT OF WAY, OR VISIBILITY(VAM).
ALL AIRBORNE DEVICES (FLAGS, PENNANTS, BALLOONS, ETC.) ARE PROHIBITIED PER SIGN ORDINANCE 06-10-109.
MAY MOUNT ONE BANNER NOT TO EXCEED 48 SQ FT TO TENT WITHOUT ADDITIONAL PERMIT.
ANY/ALL FOOD PROVISIONS MUST BE APPROVED BY THE HEALTH AND FOOD SAFETY DEPARTMENT AND MAY REQUIRE A SEPERATE TEMPORARY HEALTH PERMIT.
SUBJECT TO APPROVAL BY FIRE MARSHALL AND POLICE DEPARTMENT.
PERMIT VALID 05/03/10 THRU 05/10/10
1.Please contact the Fire Marshal’s Office for inspection.
2.Tent cannot obstruct the fire lane or vehicular traffic flow.
3.If applicable, the generator will need to be placed a minimum of 20 ft from tent.
4.Need to post the occupant load. Occupant load is 14 occupants max.
5.Need (2) exits spaced at equal intervals around the perimeter of the tent.
6.Each exit must be a minimum of 72 inches wide.
7.Need to provide (1) 2A10BC “ABC” fire extinguisher.
8.The fire extinguisher must have a current inspection tag.
9.The fire extinguisher be placed in the path of egress and mounted so that its top is not more than 5 feet above the floor.
10.Need to provide “NO SMOKING” signs.
11.Smoking, open flames or cooking is not permitted under tent structures.
12.Must meet all the minimum requirements of the International Fire Code and Building Code.
13.Need to obtain a building department inspection.
14.Additional requirements might be required when a site inspection is conducted.