Notes:
10/31/2019 10:42:10 AM
MINIMUM DUAL MAIN DRAINS REQUIRED FOR EACH SUCTION PUMP. MUST PROVIDE APPROVED DRAIN COVERS OR GRATES (ASME/ANSI A112.19.8M). COVERS MUST NOT HAVE WATER FLOW THAT EXCEEDS THE APPROVED MAXIMUM GALLONS PER MINUTE AS LISTED ON THE COVER. IF 18 X18 GRATES PROVIDED, THE FLOW MUST NOT EXCEED 1.5 FPS THROUGH REMAINING DRAIN/GRATE WITH ONE DRAIN/GRATE 100% BLOCKED. COVERS OR GRATES MUST HAVE MINIMUM OF 3’ SEPARATION, MAXIMUM 20’ INSIDE EDGES OF COVER TO COVER OR GRATE TO GRATE.
FOUNTAIN DEPTH CANNOT EXCEED 18”. IF FOUNTAIN IS NOT USING FRESHWATER, CIRCULATION EQUIPMENT SHALL BE PROVIDED AND DESIGNED TO MAINTAIN A HEALTHY FOUNTAIN ENVIRONMENT. PROVIDE OBSERVABLE WASTE WATER DISCHARGE, SITE GLASS OR FREE FALL.
PROVIDE POST CONSTRUCTION ENGINEER LETTER PRIOR TO POOL FINAL.
PROVIDE LETTER FROM PROPERTY MANAGEMENT STATING THAT THE FILTER WILL BE CLEANED AT MOP SINK ON PROPERTY.
MUST MEET REQUIREMENTS OF ALL BUILDING CODES AS AMENDED AND ADOPTED. MAKE UP WATER REQUIRES RPZ.
ENSURE NO ENTRAPMENT HAZARDS. CONTRACTOR REQUIRED TO COMPLY WITH ALL ORDINANCES. DOCUMENTATION IS AVAILABLE TO ASSIST YOU AT CITY OFFICES. LIGHTS MUST BE PROTECTED BY GFCI. EQUIPMENT ELECTRICAL DISCONNECT MUST BE VISIBLE INSIDE EQUIPMENT ROOM. APPROVED PERMIT SET OF PLANS MUST BE ON JOBSITE AT ALL TIMES. A MINIMUM OF TWO (2) SIGNS MUST BE PLACED AROUND COPING OR FOUNTAIN WALL, STATING "FOUNTAIN - NO SWIMMING - NO DIVING". CIRCULATION SYSTEMS CONSISTING OF PUMPS, PIPE, FILTERS, AND AUTOMATED DISINFECTION DEVICE SHALL BE PROVIDED AND DESIGNED TO MAINTAIN A HEALTHY FOUNTAIN ENVIRONMENT. MUST MAINTAIN STATE MINIMUM STANDARDS FOR WATER QUALITY.
MUST HAVE AN ELECTRICAL FINAL BEFORE POOL FINAL.