Notes:
12/29/2017 3:24:39 PM
PROJECT MUST COMPLY WITH POOL ORDINANCE, TDSHS MINIMUM STANDARDS FOR POOLS AND SPAS, PIWF LAW AND ADA RULES. THIS INCLUDES SITE DECK AND POOL LIGHTING, RESTROOMS, ON-DECK SHOWER, EMERGENCY PHONE, POOL ENCLOSURE AND LIFEGUARD REGULATIONS.
ENCLOSURE MUST COMPLY WITH HEALTH & SAFETY SECTION 265.200.
GATES/DOORS OF THE POOL ENCLOSURE MUST SELF-CLOSE, SELF-LATCH, BE LOCKABLE. LATCH MECHANISM MUST BE HAND ACTIVATED AND LOCATED AT LEAST 3.5FT ABOVE THE DECK (INCLUDING ANY PANIC HARDWARE).
GATE/DOORS OF THE POOL ENCLOSURE MUST OPEN AWAY FROM THE POOL, BUILDING WINDOWS MAY NOT OPEN INTO POOL ENCLOSURE. ALL GATES/DOORS EXITING A POOL YARD SHALL OPEN INTO A PUBLIC AREA OR WALKWAY ACCESSIBLE BY ALL USERS OF POOL; NO GATES/DOORS MAY OPEN DIRECTLY TO OUTSIDE OF BUILDING FROM POOL ENCLOSURE.
PROVIDE SVRS; A SVRS REQUIRED FOR COVERS OR GRATES LESS THAN 24-INCH DIAGONAL IN WATER 4 FT DEEP OR LESS.
MUST PROVIDE HI/LO DRINKING FOUNTAIN. COORDINATION WITH POOL CONTRACTOR IS IMPERATIVE.
EMERGENCY SHUT-OFF LOCATED WITHIN SIGHT OF SPA.
EMERGENCY SHUT-OFF CLEARLY LABELED AS “EMERGENCY SPA SHUTOFF”.
EMERGENCY SHUTOFF READILY ACCESSIBLE TO SPA USERS.
EMERGENCY SHUTOFF NO CLOSER THAN 5 FT UNLESS SWITCH IS NON-ELECTRICAL AIR SWITCH.
PROVIDE 1 SET OF SAFETY EQUIPMENT.
JOINTS AT COPING AND CONCRETE DECKS SHALL BE WATERTIGHT. DECK EDGES MUST BE ROUNDED, TAPERED OR SHAPED TO ELIMINATE SHARP CORNERS. DECK DRAINS SHALL NOT MIX WITH POOL WATER. SITE MUST BE GRADED TO DRAIN AWAY FROM POOL.
DECKS MUST MEASURE AT LEAST 4FT WIDE AROUND THE ENTIRE POOL WITHOUT OBSTRUCTIONS.
ALL SUCTION SUMPS MUST BE INSTALLED PRIOR TO B-STEEL INSPECTION.
EACH SUCTION SYSTEM INCLUDING CIRCULATION, BOOSTERS, WATER FALLS AND FEATURES MUST HAVE AN APPROVED ASME/ANSI A112.19.17 SVRS AND BE INSTALLED BY A CERTIFIED INSTALLER TRAINED AND CERTIFIED BY THE MANUFACTURER OF THE DEVICE.
ALL AUTO FILL LINES MUST HAVE RPZ.
DECK MARKERS MUST BE POSITIONED FOR USERS ENTERING THE POOL, 4 INCHES IN HEIGHT, AND WITHIN 24 INCHES OF WATER. PERMANENT IN NATURE, FLUSH MOUNTED (NO PAINT, NO VINYL LETTERS). PROVIDE “NO DIVING” WITH INTERNATIONAL SYMBOL TILES ALSO EVERY 25FT AROUND POOL. LITHOCHROME PAINT WILL BE REQUIRED TO BE REDONE WHEN FADED OR OTHERWISE ILLEGIBLE.
PROVIDE ALL GAUGES FOR CIRCULATION SYSTEM (VAC, PRESSURE & FLOWMETER).
MUST LABEL CIRCULATION PIPING WITH FUNCTION AND FLOW DIRECTION.
PROVIDE MEANS TO OBSERVE WASTE DISCHARGE EITHER BY FREE FALL OR SIGHT GLASS; SIGHT GLASS MUST BE REMOVABLE FOR CLEANING.
COPING, HANDHOLDS, ROCKS, STONES, OR OTHER MATERIALS THAT ARE PART OF WATER OR OTHER
FEATURES MAY NOT PROTRUDE MORE THAN 2" PAST THE POOL BEAM.
RETURN INLETS MUST NOT PROJECT MORE THAN 1 INCH BEYOND WALL.
1 SKIMMER MUST BE PROVIDED PER 500 FT FOR POOL. (POOL-3 REQUIRED/6 PROVIDED)
1 RETURN INLET FOR EVERY 300 FT FOR POOL. (POOL-5 REQUIRED/12 PROVIDED)
HAND RAIL DISTANCES ON LADDERS MUST BE 17 INCHES TO 24 INCHES.
STAIRS, LADDERS & SUNSHELF MUST HAVE A SLIP-RESISTANT SURFACE.
MUST PROVIDE PUMP SHUT OFF VALVES WHERE PUMP IS BELOW POOL ELEVATION.
MUST HAVE GFCI PROTECTION ON LIGHTING.
MUST PROVIDE ELECTRICAL DISCONNECT FOR SERVICE PERSONNEL LOCATED WITHIN SIGHT OF EQUIPMENT.
ADA POOL LIFT MUST BE PERMANENTLY BOLTED TO DECK MUST BE LOCATED IN SHALLOW AREA WHERE CHAIR CAN SUBMERGE TO AT LEAST 18 INCHES UNOBSTRUCTED. ADA POOL LIFT CAN NOT BE LOCATED AT ANY STEPS & MUST BE LOCATED IN WATER EQUAL TO OR LESS THAN 4 FT.
ALL SIGNAGE MUST COMPLY WITH SECTION 256.199 & CITY ORDINANCE; ALL SIGNAGE REQUIREMENTS CAN BE FOUND ON THE PLAN SUBMITTAL DOCUMENTS OR COMMERCIAL POOL AND SPA, PLAN DESIGN, REVIEW AND CONSTRUCTION CHECKLIST & ON (SP4.1)
IF LIFEGUARD IS PROVIDED OTHER REQUIREMENTS APPLY.
HOT AND COLD WATER ARE REQUIRED AT PUBLIC LAVATORIES AND SHOWER; WATER SUPPLIED MUST BE TEMPERED VIA THERMOSTATIC MIXING VALVE TO MAXIMUM 110 DEGREES.
RESTROOMS AND RELATED FACILITIES SERVING POOL AREA MUST COMPLY WITH POOL ORDINANCE. RESTROOMS SHALL HAVE BABY CHANGING TABLES. WOMEN’S SHALL HAVE COVERED TRASH CAN OR FEMININE WASTE RECEPTACLE WITH COVER.
LIGHTING FOR DECKS AND WATER SURFACES SHALL BE SPACED TO PROVIDE ILLUMINATION TO ALL PORTIONS OF THE DECK AND WATER SURFACE AREAS; BE NOT LESS THAN 0.5 WATTS PER SQ. FT. OF COMBINED WATER/DECK SURFACE AREAS. IF UNDERWATER LIGHTING IS PROVIDED AND IS 0.5 WATT PER SQ. FT WATER SURFACE AREA, THIS AREA NEED NOT BE CALCULATED IN DECK LIGHTING REQUIREMENT. CALL IN ELECTRICAL FINAL BEFORE HEALTH FINAL.