Notes:
SEMI PUB POOLS / ALTA FRISCO SQUARE
11/21/2017 10:27:06 AM
-LOCATE 911 PHONE TO OUTSIDE POOL ENCLOSURE. 911 PHONE MUST BE LOCATED OUTSIDE OF FENCE ENCLOSURE, WITHIN 100 FT OF POOL.
-LOCATE POOL EQUIPMENT ROOM; CLARIFY ELECTRICAL DISCONNECT LOCATION.
-LOCATE HI-LOW DRINKING FOUNTAIN ON POOL PLANS.
-LOCATE RESTROOMS ON POOL PLANS.
-HANDICAP SLEEVE CAN NOT BE LOCATED AT ANY STEPS. HANDICAP SLEEVE MUST BE LOCATED IN WATER 4 FT OR LESS.
FLOOR INLETS REQUIRED IN WATER LESS THAN 1.5 FT (1 PER 200 SQ)
RETURN INLETS MUST NOT PROJECT MORE THAN 1 INCH BEYOND WALL.
1 RETURN INLET FOR EVERY 300 SQUARE FEET. RETURNS (10 REQUIRED/12 PROVIDED)
1 SKIMMER MUST BE PROVIDED PER 500 FT FOR POOL. SKIMMERS (6 REQUIRED/6 PROVIDED)
L-3.2-PROJECT MUST COMPLY WITH POOL ORDINANCE, TDSHS MINIMUM STANDARDS FOR POOLS AND SPAS, HEALTH & SAFETY CODE CHAPTER 757 AND PIWF LAW AND ADA RULES. THIS INCLUDES SITE DECK AND POOL LIGHTING, RESTROOMS, ON-DECK SHOWER, EMERGENCY PHONE, POOL ENCLOSURE AND LIFEGUARD REGULATIONS. COORDINATION WITH POOL CONTRACTOR IS IMPERATIVE. DOOR/GATE LATCHING HARDWARE MUST BE AT 60 INCHES OR LOWER IF: 1. LATCH LOCATED AT LEAST 3 INCHES BELOW TOP PORTION OF GATE AND, 2. METAL MESH NOT TO EXCEED 0.05 INCH OPENINGS IS PROVIDED IN ALL DIRECTIONS WITHIN 18 INCHES OF THE LATCH. –OR- THE LATCH CAN BE LOCATED AT A MIN. OF 42 INCHES OR ABOVE IF IT CANNOT BE OPENED BY KEY, CARD OR COMBINATION ON BOTH SIDES OF GATE.
MUST PROVIDE A MINUMUM OF 2 SET OF SAFETY EQUIPMENT.
PROVIDE SOLID OR BROKEN VISUAL WARNING STRIP (1 INCH) UNDERWATER STEPS, UNDERWATER SEATING & WATER LOUNGES.
JOINTS AT COPING AND CONCRETE DECKS SHALL BE WATERTIGHT. DECK EDGES MUST BE ROUNDED, TAPERED OR SHAPED TO ELIMINATE SHARP CORNERS. DECK DRAINS SHALL NOT MIX WITH POOL WATER. SITE MUST BE GRADED TO DRAIN AWAY FROM POOL.
MUST PROVIDE ELECTRICAL DISCONNECT FOR SERVICE PERSONNEL LOCATED WITHIN SIGHT OF EQUIPMENT.
“NO DIVING” & INTERNATIONAL SYMBOL MUST BE 4 INCH LETTERING AND BE SPACED AT A MAX 25 FT INTERVALS. MUST PROVIDE DEPTH MARKERS WITHIN 24" OF WATERS EDGE.
ALL SUCTION SUMPS MUST BE INSTALLED PRIOR TO B-STEEL INSPECTION.
EACH SUCTION SYSTEM INCLUDING CIRCULATION, BOOSTERS, WATER FALLS AND FEATURES MUST HAVE AN APPROVED ASME/ANSI A112.19.17 SVRS AND BE INSTALLED BY A CERTIFIED INSTALLER TRAINED AND CERTIFIED BY THE MANUFACTURER OF THE DEVICE.
ALL AUTO FILL LINES MUST HAVE RPZ.
NO DOORS OF CLUBHOUSE, SALES OFFICE OR OTHER BUILDING SHALL OPEN DIRECTLY INTO THE POOL YARD UNLESS FOR ENTRY INTO STORAGE ROOM, RESTROOM, SHOWER, DRESSING OR MECHANICAL ROOM AND THE ROOM DOES NOT HAVE ANY DOOR OR GATE OPENINGS TO THE OUTSIDE OF THE POOL YARD OR ENCLOSURE.
HOT AND COLD WATER ARE REQUIRED AT PUBLIC LAVATORIES; WATER SUPPLIED MUST BE TEMPERED VIA THERMOSTATIC MIXING VALVE TO MAXIMUM 110 DEGREES.
RESTROOMS AND RELATED FACILITIES SERVING POOL AREA MUST COMPLY WITH POOL ORDINANCE. RESTROOMS SHALL HAVE BABY CHANGING TABLES. WOMEN’S SHALL HAVE COVERED TRASH CAN OR FEMININE WASTE RECEPTACLE WITH COVER.
LIGHTING FOR DECKS AND WATER SURFACES SHALL BE SPACED TO PROVIDE ILLUMINATION TO ALL PORTIONS OF THE DECK AND WATER SURFACE AREAS; BE NOT LESS THAN 0.5 WATTS PER SQ. FT. OF COMBINED WATER/DECK SURFACE AREAS. IF UNDERWATER LIGHTING IS PROVIDED AND IS 0.5 WATT PER SQ. FT WATER SURFACE AREA, THIS AREA NEED NOT BE CALCULATED IN DECK LIGHTING REQUIREMENT.
ENSURE ALL GAUGES ARE INSTALLED ON EQUIPMENT; PER SUCTION SYSTEM: VACUUME, 1-PRESSURE INLET, 1-PRESSURE OUTLET, 1 FLOW METER. MUST LABEL CIRCULATION PIPING WITH FUNCTION AND FLOW DIRECTION.
ALL SIGNAGE MUST COMPLY WITH SECTION 256.199 & CITY ORDINANCE; ALL SIGNAGE REQUIREMENTS CAN BE FOUND ON THE PLAN SUBMITTAL DOCUMENTS OR COMMERCIAL POOL AND SPA, PLAN DESIGN, REVIEW AND CONSTRUCTION CHECKLIST. Including but not limited to the following (If lifeguard provided, other signs may apply):
o 1. “WARNING – NO LIFEGUARD ON DUTY” (letters 4” high or higher) where applies.
o 2. “CHILDREN SHOULD NOT USE POOL WITHOUT ADULT SUPERVISION”*: (letters must be 2” high or higher)
o 3. “NO DIVING” and the International Symbol for No Diving (letters 4” high or higher) (Required in decking or coping also)
o 4. “ADULTS SHOULD NOT SWIM ALONE”
o 5. “FOR EMERGENCY DIAL 911” (letters 4” high or higher)
o 6. “NO GLASS IN POOL AREA”
o 7. “SWIMMERS MUST SHOWER BEFORE ENTERING SWIMMING POOL/SPA”
o 8. “NO ANIMALS IN POOL AREA”
o 9. Maximum pool load limits shall be posted. (LOAD: 169)
o 10. General pool rules shall be posted.
COPING, HANDHOLDS, ROCKS, STONES, OR OTHER MATERIALS THAT ARE PART OF WATER OR OTHER FEATURES MAY NOT PROTRUDE MORE THAN 2" PAST THE POOL BEAM.