2 POOLS, 2 SPAS / PRESTIGE POOLS
8/19/2015 12:00:00 AM
PENDING: POOL ENCLOSURE DETAILS. SEE SP1 FOR GROTTO REINFORCEMENT SCHEDULE.
PROVIDE SIGN ACROSS SLIDE STATING 'CLOSED' WHEN BUSINESS IS CLOSED.
PROVIDE ACCESSIBLE SLEEVE AT EACH POOL FOR ADA COMPLIANCE.
PROVIDE SIDE WALL DEPTH MARKERS, MIN. 4 INCH HEIGHT, CONTRASTING IN COLOR.
PROVIDE SIGNAGE STATING PHONE LOCATION (FOR SUMMONING EMERGENCY PERSONNEL) AT EACH ENTRANCE. PROVIDE WRITTEN INSTRUCTIONS AT NEAREST PHONE REGARDING DIALING 9-1-1.
MUST PROVIDE VISUAL SEPARATION (MIN. 4 INCH TILE STRIPE) AT TANNING LEDGE (POOL A) AND AT FOOT REST/ FLOATING TABLE (POOL B) AND ANY AREA UNDER WATER LEVEL THAT IS 10 INCH DEPTH OR LESS.
PROJECT MUST COMPLY WITH SITE DECK AND POOL LIGHTING REQUIREMENTS. MUST PROVIDE
ENSURE FIRE FEATURE SET BACK TO ARBOR (CLARIFICATION NEEDED IF UL LISTED APPLIANCE).
PROVIDE SIGNAGE AT GROTTO ‘NO DIVING’.
BACKWASH MUST BE IN SIGHT OF EQUIPMENT.
MUST PROVIDE ELECTRICAL DISCONNECT WITHIN SIGHT OF EQUIPMENT.
MUST PROVIDE SHUT OFF BUTTON FOR SPA WITHIN ENCLOSURE, AT LEAST 5 FT. FROM WATER’S EDGE.
DOORS OF SALES OFFICE OR OTHER BUILDING SHALL NOT OPEN DIRECTLY INTO THE POOL YARD UNLESS FOR ENTRY INTO STORAGE ROOM, RESTROOM, SHOWER, DRESSING OR MECHANICAL ROOM AND THE ROOM DOES NOT HAVE ANY DOOR OR GATE OPENINGS TO THE OUTSIDE OF THE POOL YARD OR ENCLOSURE.
LIGHTING FOR DECKS AND WATER SURFACES SHALL BE SPACED TO PROVIDE ILLUMINATION TO ALL PORTIONS OF THE DECK AND WATER SURFACE AREAS; BE NOT LESS THAN 0.5 WATTS PER SQ. FT. OF COMBINED WATER/DECK SURFACE AREAS. IF UNDERWATER LIGHTING IS PROVIDED AND IS 0.5 WATT PER SQ. FT WATER SURFACE AREA, THIS AREA NEED NOT BE CALCULATED IN DECK LIGHTING REQUIREMENT.