Notes:
SPRAY PARK
6/13/2008 12:00:00 AM
COMMENTS FROM HEALTH & FOOD SAFETY
STONEBRIAR CC SPRAY PARK:
- SPECIAL AQUATIC ACTIVITY DEVICE/SPRAY PARK MUST BE DESIGNED AND CONSTRUCTED IN ACCORDANCE WITH SECTION 265.199 OF THE STATE MINIMUM STANDARDS.
- CIRCULATION SYSTEM MUST TURNOVER < OR = 30 MINUTES.
- MUST HAVE POTABLE WATER FOR RE OR AUTO FILL.
- FILTRATION SYSTEM MUST BACKWASH TO SANITARY SEWER SYSTEM.
- MUST HAVE AUTO DISINFECTION/CHEMICAL SYSTEM AND MAINTAIN STATE MINIMUM STANDARDS FOR WATER QUALITY.
- MUST MEET APPLICABLE ELECTRIC & PLUMBING CODES.
- SPRAY PARK BARRIER INCLUDING ALL ENTRIES/EXITS MUST MEET STATE MINIMUM STANDARDS.
- RESTROOM LAVATORIES AND SHOWER MUST HAVE TEMPERED HOT WATER (90 - 110 DEGREES) AND DRAIN TO SANITARY SEWER.
- PROVIDE AND LOCATE WATER DRINKING FOUNTAINS.
- EQUIPMENT ELECTRICAL DISCONNECT MUST BE VISIBLE INSIDE POOL EQUIPMENT ROOM.
- PROVIDE AND LOCATE KNOX BOX LOCATED OUTSIDE OF POOL BARRIER.
- POST CONTRUCTION ENGINEERS LETTER TO BE ONSITE AT POOL FINAL.
- APPROVED PERMIT SET OF PLANS TO BE ON JOBSITE AT ALL TIMES.
- POOL BACKWASH MUST BE PLUMBED TO AIR GAP & P-TRAP AND DRAIN TO SANITARY SEWER LINE.
- SPRAY PARK PAD SHALL BE CONTRUCTED & GRADED TO MINIMIZE STORM WATER TO DECK DRAINS CATCHING RUN OFF PIPED TO COLLECTOR TANK.
- COLLECTION TANK MUST HAVE OVERFLOW LEVEL TO PREVENT POSSIBILITY OF SUCTION AT DRAIN.
- PROVIDE OBSERVABLE WASTE WATER DISCHARGE, SITE GLASS OR FREE FALL. RETURN WATER TO BE TREATED AND AUTOMATICALLY DISINFECTED.
- PERMANENTLY LABEL ALL EXPOSED PIPING AT EQUIPMENT.
- EQUIPMENT ROOM INCLUDING ACCESS TO COLLECTOR TANK MUST BE LOCKABLE AND REMAIN LOCKED TO PREVENT UNAUTHORIZED ACCESS.
- TEST PORT ON RETURN SIDE OF AUTO DISINFECTANT EQUIPMENT IN ORDER TO SAMPLE WATER.
- STORAGE ROOM VENTILATED IF USED TO STORE CHEMICALS.
- SPRAY PARK (WATER & EQUIPMENT) MUST BE MAINTAINED BY A CERTIFIED POOL OPERATOR (CPO).