Notes:
SPA ONLY / THE LODGE AT FRISCO BRIDGES
9/27/2007 12:00:00 AM
COMMENTS FROM HEALTH & FOOD SAFETY:
LODGE AT FRISCO BRIDGES SPA AND POOL/SPA BARRIER:
- POOL BARRIER MUST BE BROUGHT UP TO CODE. POOL BARRIER INCLUDING ALL ENTRIES/EXITS MUST MEET STATE MINIMUM STANDARDS. SPACING IN FENCE NOT EXCEED 4 INCHES. GATES TO SELF CLOSE AND LATCH AND BE LOCKABLE. NO GAPS > ½ " WITHIN 18" OF THE LATCH MECHANISM. BARRIER MAY NOT HAVE CLIMB HAZARDS AND CLIMB HAZARDS MAY NOT EXIST WITHIN 3 FT OF ANY PART OF BARRIER.
- EQUIPMENT ROOM MUST HAVE ADEQUATE VENTILATION - LOUVERED OR MECHANICAL - AND HAVE LOCKABLE ACCESS.
- ALL LEADING EDGES OF BENCHES, STEPS AND LEDGES REQUIRE 1 INCH MINIMUM TILE STRIPE.
- LIGHTS MUST BE PROTECTED BY GFCI. EQUIPMENT ELECTRICAL DISCONNECT MUST BE VISIBLE INSIDE POOL EQUIPMENT ROOM.
- AUTOFILL LINE, IF PROVIDED, MUST NOT PROTRUDE BEYOND COPING EDGE.
- DEPTH, NO DIVING, AND INTERNATIONAL SYMBOL MARKERS MUST BE PROVIDED MINIMUM OF EVERY 25 FT. MINIMUM OF 2 EACH ON SPA.
- SKIMMER EQUALIZER LINES ARE NOT ALLOWED.
- POST CONTRUCTION ENGINEERS LETTER TO BE ONSITE AT POOL FINAL.
- APPROVED PERMIT SET OF PLANS TO BE ON JOBSITE AT ALL TIMES.
- ALL SIGNAGE REQUIRED BY STATE CODE AND POOL ORDINANCE MUST BE INSTALLED AT POOL FINAL.
- EMERGENCY SHUT OFF SWITCH REQUIRED FOR SPA MINIMUM 5 FT AWAY FROM WATERS EDGE. AIR BLOWERS REQUIRE 15 MINUTE TIMER SHUTOFF. SIGN TO STATE "EMERGENCY SPA PUMP SHUTOFF"
- ALL SPA SIGNAGE REQUIRED TO BE POSTED AT FINAL INSPECTION.
- PERMIT TO OPERATE MUST BE OBTAINED PRIOR TO OPENING SPA.
- SPA REQUIRES SVRS.
- NO MORE THAN 50% OF THE SPA DECK CAN BE REPLACED WITH OTHER STRUCTURE. DECK MUST BE MINIMUM 4FT IN WIDTH.