Notes:
POOL BARRIER INCLUDING ALL ENTRIES/EXITS MUST MEET STATE MINIMUM STANDARDS. SPACING IN FENCE NOT EXCEED 4 INCHES. GATES TO SELF CLOSING/LATCHING AND BE LOCKABLE. NO CLIMB HAZARDS WITHIN 36" OF BARRIER. NO GAPS > ½" WITHIN 18" OF LATCH MECHANISM, IN ALL DIRECTIONS. PROVIDE AND LOCATE EMERGENCY 911 PHONE OUTSIDE OF POOL BARRIER. EQUIPMENT ROOM MUST HAVE ADEQUATE VENTILATION - LOUVERED OR MECHANICAL - AND HAVE LOCKABLE ACCESS. ALL LEADING EDGES OF BENCHES, STEPS AND LEDGES REQUIRE 1 INCH MINIMUM TILE STRIPE. LIGHTS MUST BE PROTECTED BY GFCI. PROVIDE AND LOCATE CHAIRLIFT SLEEVE. SLEEVE MUST BE BONDED. OUTDOOR POOL CHAIRLIFT SLEEVE SHALL BE WITHIN 24 INCHES OF WATER'S EDGE. SEE ATTACHED CHECKLIST FOR GUIDELINES ON SIGNAGE REQUIREMENTS. TWO SETS OF SAFETY EQUIPMENT ARE REQUIRED ON POOLS OVER 2000 SQ FT. AUTOFILL LINE, IF PROVIDED, MUST NOT PROTRUDE BEYOND COPING EDGE. PROVIDE AND LOCATE KNOX BOX LOCATED OUTSIDE OF POOL BARRIER. DEPTH MARKERS AND "NO DIVING AND INTERNATIONAL SYMBOL" MUST BE PROVIDED MINIMUM OF EVERY 25 FT. ENTRY/EXITS MUST BE PROVIDED EVERY 75 FT. OF POOL WALL LENGTH OR FRACTION OF. SKIMMER EQUALIZER LINES ARE NOT ALLOWED. PROVIDE AND LOCATE DRINKING WATER FOUNTAINS. ELECTRICAL DISCONNECT WITHIN SIGHT OF POOL EQUIPMENT. SPA REQUIRES 15 MINUTE MANUAL TIMER & EMERGENCY PUMP SHUT OFF SWITCH INSTALLED ACCORDING TO CODE AND WITH PROPER SIGNAGE. DECORATIVE FOUNTAIN MUST BE PERMITTED SEPERATELY.
POOL / PARKVIEW SENIOR RESIDENCE