Notes:
POOL AND SPA
2/27/2006 12:00:00 AM
1. DUAL MAIN DRAINS REQUIRED WITH MINIMUM SEPERATION OF 3 FT BETWEEN INSIDE EDGES OF DRAIN COVERS.
2. DIVING BOARD AND ENVELOPE TO MEET NSPI STANDARDS.
3. TURNOVER RATE TO BE LESS THAN 6 HOURS.
4. GAS VENT TO BE 5 FT AWAY FROM ANY OPENABLE WINDOW.
5. WINDOWS WITHIN 36" OF WALKWAY OR <5' TO WATER MUST BE SAFETY GLAZED TO CODE.
6. CERTIFICATION OF POOL PROTECTION DEVICE INSTALLATION TO BE SIGNED AND ON SITE AT PRE-PLASTER INSPECTION.
7. CONTRACTORS: IT IS YOUR RESPONSIBILITY TO INFORM THE HOMEOWNER OF THE NECESSITY OF INSPECTORS TO GAIN ACCESS TO THE BACKYARD.
SLIDE TO MEET CPSC STANDARDS, AND BE INSTALLED ACCORDING TO MANUFACTUR’S REQUIREMENTS, INCLUDING DESIGNed SLIDE ENVELOPE AND DEPTH REQUIREMENTS
(2/27/2006 15:41 JKT)
MDX SYSTEMS FOR POOL AND SPA MUST BE INSTALLED ACCORDING TO MANUFACTURERS REQUIREMENTS, AND THE PLAN DRAWINGS/DIAGRAMS SUBMITTED.
OUTDOOR KITCHENS, ARBORS, PATIO COVERS, BBQ GRILL, FIRE PIT, FIRE PLACE AND FENCES MUST BE PERMITTED SEPARATELY.