Notes:
12-07-05 JM)
1. 2 exits are required at pool area ---330 occupants.
2. included are revisions to both restrooms to accommodate occupant load.
3. resubmit new plbg. riser diagram for additional plbg. fixtures.
4. handrails are req'd. at entries to pool areas (steps down into water area) at tot pool also.
5. 100% visual screening enclosure trash facility, coordinate with environmental services department for approval, include additional sidewalk for commercial totes.
6. 1 hose bibb is req'd.
(2/9/2006 15:56 JKT)
GRAYHAWK - EL DORADO RANCH
SPACING IN FENCE RODS OR FENCE GAPS, NOT TO EXCEED 4 INCHES. GATES TO SELF CLOSING/LATCHING AND BE LOCKABLE. RESTROOM LAVATORIES AND SHOWER MUST HAVE HOT WATER AND DRAIN TO SANITARY SEWER. EQUIPMENT ROOM MUST HAVE ADEQUATE VENTILATION - LOUVERED OR MECHANICAL - AND HAVE LOCKABLE ACCESS. ALL LEADING EDGES OF BENCHES, STEPS AND LEDGES REQUIRE 1 INCH MINIMUM TILE STRIPE. LIGHTS MUST BE PROTECTED BY GFCI. CHAIRLIFT SLEEVE SHALL BE WITHIN 24 INCHES OF WATER'S EDGE. SEE ATTACHED CHECKLIST FOR GUIDELINES ON SIGNAGE REQUIREMENTS. TWO SETS OF SAFETY EQUIPMENT ARE REQUIRED. AUTOFILL LINE, IF PROVIDED, MUST NOT PROTRUDE BEYOND COPING EDGE. KNOX BOX LOCATED OUTSIDE OF POOL BARRIER. PROVIDE AND LOCATE WATER FOUNTAINS. REST ROOMS REQUIRE BABY CHANGING STATIONS. "NO DIVING AND INTERNATIONAL SYMBOL MUST BE PROVIDED MINIMUM OF EVERY 25 FT. - MAIN POOL -2140 SQ. FT. ENGINEER REQUIRES 5 SKIMMERS, 12 RETURN INLETS, KIDDIE POOL - 314 SQ. FT. ENGINEER REQUIRES 1 SKIMMER, 3 RETURN INLETS
BATHER LOAD: LG. POOL = 120 PERSONS. KIDDIE POOL = 20
(2/9/2006 15:57 JKT)
ENGINEERS LETTER ON FILE. PLAN REVIEW CONDUCTED BY JS & JKT.
POOL ONLY