Permit Info
Short Description:
Replaced existing retail area ac system, ducting
Expiration Date:
3/30/2019
Notes:
9/28/2018 6:12:06 AM
10/1/2018 2:25:10 PM
REPLACING 5 TON UNIT WITH NEW 5 TON UNIT AND REPLACING DUCTING.
STANDARD MECHANICAL COMMENTS:
401. ALL WORK PERFORMED MUST MEET THE 2015 IRC AND 2015 IMC STANDARDS AND ABIDE BY THE CITY OF FRISCO COMPREHENSIVE ZONING ORDINANCE, AND ALL OTHER CITY ORDINANCES.
402. SUBJECT TO FIELD INSPECTION APPROVAL. CALL (972) 292-5386 FOR INSPECTION.
403. ALL DUCT WORK TO BE SEALED WITH MASTIC, WELDS, OR GASKETS; TAPES ARE NOT ALLOWED.
404. ALL EXHAUST TO TERMINATE OUTSIDE OF THE BUILDING. PRESSURE EQUALIZATION IS REQUIRED FOR ALL EXHAUST SYSTEMS (SEE IMC 501.3).
405. ELECTRICAL ROOMS ARE REQUIRED TO BE VENTILATED (SEE NEC 110.13B AND IMC CHAPTER 4).
406. MECH. ENGINEER AND CONTRACTOR TO BE RESPONSIBLE FOR LOAD CALCULATIONS AND DUCT SIZING (SEE IMC SECTION 312 AND SECTION 603.2). ALL CALCULATIONS WILL BE SUBJECT TO REQUEST FOR PLAN REVIEW.
407. MECH. ENGINEER TO VERIFY VENTILATION RATES ON THE SUBMITTED PRINTS (SEE IMC SECTION 403 AND AMENDMENTS 08-01-11).
408. MECH. INSTALLATION TO COMPLY WITH THE CURRENT FRISCO AMENDMENTS (08-01-11 OF THE IMC AND IECC).
409. RIGID DUCT IS REQUIRED FOR ALL HVAC APPLICATIONS. A 6 FT (R-6) FLEX DUCT CONNECTOR IS ALLOWED BETWEEN RIGID DUCT AND CEILING DIFFUSERS.
410. PIPING INSULATION EXPOSED TO WEATHER SHALL BE PROTECTED FROM DAMAGE, INCLUDING THAT CAUSED BY SUNLIGHT, MOISTURE, EQUIPMENT MAINTENANCE, AND WIND AND SHALL PROVIDE SHIELDING FROM SOLAR RADIATION THAT CAN CAUSE DEGRADATION OF THE MATERIAL. ADHESIVE TAPE SHALL NOT BE PERMITTED.
Parcel Info
City/State/Zip:
FRISCO, TX, 75034
Subdivision:
CRESTVIEW INDUSTRIAL PARK (CFR)
|
OWNER | OLD DONATION LLC | (214)534-3968 | | C/O RICK KEYSON | FRISCO, TX 75033 - 2701 |
APPLICANT | A/C UNLIMITED INC | (972)533-4684 | acunlimited@yahoo.com | 9866 Camfield Ave | FRISCO, TX 75033 |
CONTRACTOR | A/C UNLIMITED INC | (972)533-4684 | acunlimited@yahoo.com | 9866 Camfield Ave | FRISCO, TX 75033 |
CONTACT | Troy Fewell | (972)533-4684 | troyfewell@sbcglobal.net | 9866 Camfield Ave | Frisco, TX 75033 |
MECH. CTR. | A/C Unlimited, Inc. | (972)533-4684 | acunlimited@yahoo.com | 9866 Camfield Ave | Frisco, TX 70533 |
|
MECHANICAL FEE |
$67.50
|
10/1/2018
|
OTHER FEE |
$15.00
|
10/1/2018
|
Total Fees |
Charged: $82.50
Balance Due: $0.00
|
There are currently no inspections on this record.
|
MECHANICAL REVIEW | MICHELE WOOD | APPD W/ CONDITIONS | 9/28/2018 | 10/1/2018 | |