Notes:
1- CONTINGENT UPON COMPLIANCE WITH BLDG CODE & LOCAL REQUIREMENTS, PERTINENT LEGISLATIONS AND REVIEW COMMENTS.
2- PERMIT IS NOT VALID UNLESS AN ASBESTOS SURVEY OF THE EXISTING CONSTR'N (SB 509) AND AN ASBESTOS STATEMENT FOR THE PROPOSED NEW CONSTR'N (HB 1927) ARE SUBMITTED AS PER STATE LEGISLATION.
3- SIZE OF MTL STUDS FOR DEMISING WALLS ARE PERMITTED TO BE MIN. 3-5/8" ONLY IF OF MIN. 20 GA. AND SPACED MAX. 16" O/C (OTHERWISE USE 6" STUDS). THESE WALLS MUST BE RATED AS REQ'D, FULLY FIRE SEALED TO UNDERSIDE OF DECK AND CONTAIN NO PLBG INSIDE.
4- WHERE NECESSARY, JAG THE DEMISING WALL FOR PROPER FIRE/SMOKE-RATED CONNECTION TO THE NEAREST STOREFRONT'S MULLION OR PIER AS TYPICALLY REQ'D.
5- ELECTRICAL CLOSET MUST BE ENCLOSED WITH 1 HR WALLS TO DECK OR TO THE UNDERSIDE OF APPROVED 1 HR CLG. OUTSWINGING DOOR TO BE 45 MINUTE RATED IN 1 HR FRAME.
6- HINGES OF EXISTING BACK DOOR TO BE ON THE SIDE NEXT TO KITCHEN COUNTER (DUE TO COUNTER BEEING CLOSER THAN 12" TO DOOR) AND DOOR INTO BREAKROOM TO SWING TOWARD EXITING AS REQ'D.
7- ADD UTILITY MOP SINK AS REQ'D (LOCATION OPTIONAL).
8- SUBJECT TO M.E.P. REVIEWS, FIRE MARSHAL AND FIELD INSPECTIONS.
**************ALL SUBCONTRACTORS MUST VALIDATE AND OBTAIN CURRENT REGISTRATION WITH THE CITY PRIOR TO START OF PROJECT.
10-07-05 JM)
CALLED AND SPOKE TO ELECTRICAL CONTRACTOR, EXPLAINED THAT ONE LINE DIAGRAM IS INCORRECT TO REVISE AND RESUBMIT NEW ONE LINE DIAGRAM
THIS PLAN IS ON TOM WHEELER'S DESK FOR MECHANICAL REVIEW.
REWORK HVAC SYSTEM / BAYLOR FRISCO REHAB CENTER