permanent lockout at the water heater breaker located inside the electrical panel.
- Water heaters located in attic shall have a passage way not less than 30” high with continuous solid flooring not less than 24”. A 30”x 30” level service space shall be in front of water heater. The opening shall be large enough to allow for removal.
- Minimum vertical rise for vent shall be 5’, and shall terminate not less than 8’ from vertical surface or less than 2’ above roof line.
- Vent cap, collar, and flashing shall be properly installed.
- Vents shall be adequately secured in place.
- Clearance from combustibles shall be min. 1” for doubled walled vent and 6” for
Single walled.
- Check clearance from water heater to combustibles as per name plate.
- Dissimilar metal connections shall be made with dielectric unions or brass fitting.
- Gas valve shutoff shall be of an approved type and located in the same room as water heater not further than 6’ from the appliance. Gas flex must be replaced as per manufacturer’s instructions.
- Sediment traps shall be installed as required by the current IRC, and IFGC.