Notes:
REPLACE W/H
4/19/2012 12:00:00 AM
- Water heater installation requirements
* ALL WORK PERFORMED MUST MEET THE 2006 IRC STANDARDS AND ABIDE BY THE CITY OF FRISCO COMPREHENSIVE ZONING ORDINANCE, AND ALL OTHER CITY ORDINANCES.
SUBJECT TO FIELD INSPECTION APPROVAL CALL (972) 292-5386 FOR INSPECTION.
T&P line shall discharge to outside of building and terminate not less than 6” above grade and shall not terminate on sidewalk or patio. T&P line must be installed with a union and shall not be trapped under slab or at any other location.
- Drain pans required under every water heater in all locations with drain extending to the outside minimum 6” and maximum 24” above grade. Drain pan line may be run to lowest level of garage in cases where it is not possible to run to exterior. Other methods in lieu of pan drain can be installed with prior approval.
- A means for thermal expansion control is required where a closed system is in place. A PRV is considered to create a closed system.
- When located in garage, the source of ignition shall be not less than 18” above the floor.
- Water heaters located in attic shall have a passage way not less than 30” high with continuous solid flooring not less than 24”. A 30”x 30” level service space shall be in front of water heater. The opening shall be large enough to allow for removal.
- Minimum vertical rise for vent shall be 5’ and shall terminate not less than 8’ from vertical surface or less than 2’ above roof line.
- Vent cap, collar, and flashing shall be properly installed.
- Vents shall be adequately secured in place.
- Clearance from combustibles shall be min. 1” for doubled walled vent and 6” for single walled.