Notes:
NEW WOOD FENCE 19'
8/15/2014 12:00:00 AM
(8/15/2014 9:55 AM HC)
300. FENCE:
301. *ALL FENCES MUST BE CONSTRUCTED ON OR INSIDE THE PRIVATE PROPERTY LINE.
302. *ALL VERTICAL POSTS ON FENCES OVER FOUR (4) FEET IN HEIGHT SHALL BE GALVANIZED STEEL WITH A MINIMUM 2-3/8 INCH DIAMETER, A MINIMUM FIFTEEN (15) GAUGE THICKNESS, AND SET IN AN EIGHT (8) INCH DIAMETER CONCRETE FOOTING.
303. *FOR FENCES LESS THAN SEVEN (7) FEET IN HEIGHT, POSTS SHALL BE MAXIMUM EIGHT (8) FEET ON CENTER, SET IN A CONCRETE FOOTING OF NO LESS TWENTY-FOUR (24) INCHES DEEP. FOR FENCES SEVEN (7) FEET OR GREATER IN HEIGHT, POSTS SHALL BE SPACED AT A MAXIMUM OF SIX (6) FT ON CENTER, SET IN A CONCRETE FOOTING OF NO LESS THAN THIRTY-SIX (36) INCHES DEEP.
305. *ALL WOOD MATERIAL SHALL BE STAINED, PRESSURE TREATED, PAINTED, OR ADEQUATELY SEALED TO PREVENT DECAY.
307. *DECORATIVE GATE EMBELLISHMENTS ARE ALLOWED. THEY SHALL NOT EXCEED THE HEIGHT OF THE FENCE BY MORE THAN TWO (2) FEET.
308. GATES IN FENCE SHOULD BE THREE (3) FEET MINIMUM IN WIDTH FOR EGRESS.
310. *IT IS THE APPLICANT’S RESPONSIBILITY TO VERIFY ADDITIONAL HOA REQUIREMENTS AND TO OBTAIN HOA APPROVAL IF REQUIRED. *** CALL 811 OR GO TO HTTP://TICKETS.DIGTESS.ORG TWO WORKING DAYS BEFORE DIG ***
311. RETAINING WALL:
312. * ALL RETAINING WALLS MUST BE ON OR INSIDE THE PROPERTY LINE. RETAINING WALLS IN EXCESS OF 36 INCHES IN HEIGHT MUST PROVIDE ENGINEERED PLANS. THE COMBINED HEIGHT OF RETAINING WALL AND FENCE MAY NOT EXCEED 8 FEET FROM GRADE.
313. SUBJECT TO FIELD INSPECTION APPROVAL.
314. CALL (972) 292-5386 FOR INSPECTION.
315. * PIER AND FOOTING INSPECTIONS REQUIRED PRIOR TO PLACING CONCRETE.
316. * OWNER WILL BE RESPONSIBLE FOR ANY EXPENSES DUE TO PROPERTY DAMAGE AND/OR RETAINING WALL DAMAGE BUILT IN THE UTILITY EASEMENT.