Permit Info
Short Description:
RETAINING WALL
Expiration Date:
2/9/2013
Notes:
RETAINING WALL
7/17/2012 12:00:00 AM
ENG COMMENTS:
1. Include definition of “compacted fill” in details for soil beneath the walls and behind the walls, such that it may be verified by observation in the field.
2. All section details should include the statement “no voids” when specifying mortared zones.
3. Walls with associated drainage system will require inspection and certification by the Design Engineer even if they are below three (3) feet.
4. All walls must have a minimum embedment depth of one (1) foot per the International Building Code (IBC)
BUILDING INSPECTION COMEMNTS:
1-5 FT IN HEIEHT RETAINING WALL LOCATIONS AS SPECIFIED ON SITE PLAN AND REFERENCE APPROVED PLANS.
SUBJECT TO FIELD INSPECTION APPROVAL. CALL (972) 292-5386 FOR FOOTING AND BUILDING FINAL INSPECTION REQUIRED.
SHALL NOT BE LOCATED WITH ANY DEDICATED EASEMENTS.
LETTER OF ENGINEER FINAL ACCEPTANCE REQUIRED FOR INSPECTION AND CONSTRUCTION CONFORMANCE WITH DESIGN DRAWINGS.
PROVIDE EROSION CONTROL THROUGHOUT CONSTRUCTION. PROVIDE SOIL STABILIZATION AT COMPLETION OF PROJECT.
***FLOODWAY EASEMENT SHALL NOT BE DISTURBED OR RE-GRADED FROM EXISTING CONDITIONS.
***ENGINEERS DESIGN WILL NOT SUPPORT SURCHARGE LOADS OF BUILDINGS.
***NO PORTION OF RETAINING WALL SHALL BE LOCATED IN ADJACENT FLOODWAY EASEMENT.
***GRADING CHANGE SHALL NOT OBSTRUCT DRAINAGE OF ADJACENT PROPERTIES.
***FENCE REPLACEMENT NOT SHOWN. SEPARATE PERMIT REQUIRED.
***SUBDIVISION HOA APPROVED MAY BE REQUIRED.
Parcel Info
City/State/Zip:
FRISCO, TX,
Subdivision:
RICHWOODS PH 6
|
OWNER | Richwoods Development, LLC | (214)619-2930 | jlandon@landonhomesusa.com | 4050 W. Park Blvd. | PLANO, TX 75093 |
APPLICANT | STERLING MASONRY LLC | (817)613-7840 | TSHEFT@STERLINGMASONRYLLC.COM | SUITE 267-232 | PLANO, TX 75093 |
CONTRACTOR | STERLING MASONRY LLC | (817)613-7840 | TSHEFT@STERLINGMASONRYLLC.COM | SUITE 267-232 | PLANO, TX 75093 |
|
FENCE FEE |
$20.00
|
8/13/2012
|
Total Fees |
Charged: $20.00
Balance Due: $0.00
|
There are currently no inspections on this record.
|
FENCE REVIEW | Phillip Climer | Approved | 6/29/2012 | 7/17/2012 | 7/13/2012 |
More Info
|