Notes:
INSTALL FOUR POLE LIGHTS
4/10/2014 12:00:00 AM
1. ALL WORK PERFORMED MUST MEET THE 2006 INTERNATIONAL BUILDING CODE, LOCAL AMENDMENTS AND ABIDE BY THE CITY OF FRISCO COMPREHENSIVE ZONING ORDINANCE AND ALL OTHER CITY ORDINANCES.
SUBJECT TO FIELD INSPECTION APPROVAL. CALL (972) 292-5386 FOR INSPECTIONS REQUIRED. PREPOUR FOR POLE BASE, ELECTRICAL ROUGH, ELECTRICAL FINAL INSPECTIONS REQUIRED.
Electrical
1.MINIMUM #12 COPPER CONDUCTORS PERMITTED EXCEPT FOR CONTROLS. LIGHT COMCHECK CALCULATIONS MUST MATCH PLANS.
2. ALUMINUM WIRE PERMITTED IN SERVICE ENTRANCE AND FEEDERS 1/0 AND LARGER STABIL-ALLOY SERIES 6000 & 8000.
3.PULL EQUIPMENT GROUNDS IN ALL RACEWAYS.
4.PROVIDE EXIT AND EMERGENCY LIGHTING AS NOTED AND REQUIRED PER 2006 IBC.
5.LIGHTING AND CONTROLS SHALL COMPLY WITH 2012 IECC WHERE APPLICABLE.
6. ALL EXTERIOR LIGHTING SHALL COMPLY WITH THE COMPREHENSIVE ZONING ORDINANCE ARTICLE IV SECTION 6.
7. ALL ELECTRICAL INSTALLATIONS WILL BE SUBJECT TO FIELD INSPECTIONS AND INSPECTOR APPROVALS.
8. ALL CONDUCTORS MUST TERMINATE IN DEVICES THAT HAVE BEEN PROPERLY TIGHTENED TO MANUFACTURERS’ TORQUE SPECIFICATIONS USING THE PROPER TORQUE TOOL.
10. LEGIBLE PANEL SCHEDULE SHALL BE PROVIDED AT ALL PANEL LOCATIONS.
11. ELECTRICAL WILL BE DESIGNED AND INSTALLED PER THE 2011 NATIONAL ELECTRICAL CODE WITH LOCAL AMENDMENTS STATED IN CITY OF FRISCO ORDINANCE.
12. CABLES AND CONDUITS IN PLENUMS SHALL BE RATED FOR PLENUM APPLICATIONS.
13. GROUNDING AND BONDING SHALL COMPLY WITH ARTICLE 250 2011 NEC. STRUCTURAL STEEL, GROUND ROD, COPPER DOMESTIC SERVICE (UFER IS AVAILABLE PER ARTICLE 250.81).
14. THE GROUNDED CONDUCTOR SMALLER THAN #6 AWG MUST BE WHITE OR GRAY INSULATION NO PHASING WIRES PER NEC ARTICLE 200.7.
15. THE GROUNDING CONDUCTOR SMALLER THAN #6 AWG SHALL BE GREEN INSULATION OR BARE PER NEC ARTICLE 250.119.