Notes:
EXTERIOR LIGHTING FOR GUARD HOUSE
8/1/2012 12:00:00 AM
1.MINIMUM #12 COPPER CONDUCTORS PERMITTED EXCEPT FOR CONTROLS. LIGHT COMCHECK CALCULATIONS MUST MATCH PLANS.
2. ALUMINUM WIRE PERMITTED IN SERVICE ENTRANCE AND FEEDERS 1/0 AND LARGER STABIL-ALLOY SERIES 6000 & 8000.
3.PULL EQUIPMENT GROUNDS IN ALL RACEWAYS.
4.PROVIDE EXIT AND EMERGENCY LIGHTING AS NOTED AND REQUIRED PER 2006 IBC.
5.LIGHTING AND CONTROLS SHALL COMPLY WITH 2006 IECC WHERE APPLICABLE.
6. ALL EXTERIOR LIGHTING SHALL COMPLY WITH THE COMPREHENSIVE ZONING ORDINANCE ARTICLE IV SECTION 6.
7. ALL ELECTRICAL INSTALLATIONS WILL BE SUBJECT TO FIELD INSPECTIONS AND INSPECTOR APPROVALS.
8. ALL CONDUCTORS MUST TERMINATE IN DEVICES THAT HAVE BEEN PROPERLY TIGHTENED TO MANUFACTURERS’ TORQUE SPECIFICATIONS USING THE PROPER TORQUE TOOL.
10. LEGIBLE PANEL SCHEDULE SHALL BE PROVIDED AT ALL PANEL LOCATIONS.
11. ELECTRICAL WILL BE DESIGNED AND INSTALLED PER THE 2005 NATIONAL ELECTRICAL CODE WITH LOCAL AMENDMENTS STATED IN CITY OF FRISCO ORDINANCE.
12. CABLES AND CONDUITS IN PLENUMS SHALL BE RATED FOR PLENUM APPLICATIONS.
13. GROUNDING AND BONDING SHALL COMPLY WITH ARTICLE 250 2005 NEC. STRUCTURAL STEEL, GROUND ROD, COPPER DOMESTIC SERVICE (UFER IS AVAILABLE PER ARTICLE 250.81).
14. THE GROUNDED CONDUCTOR SMALLER THAN #6 AWG MUST BE WHITE OR GRAY INSULATION NO PHASING WIRES PER NEC ARTICLE 200.7.
15. THE GROUNDING CONDUCTOR SMALLER THAN #6 AWG SHALL BE GREEN INSULATION OR BARE PER NEC ARTICLE 250.119.
*** CONTRACTOR RESPONSIBLE FOR ALL LOAD CALCULATION AND WIRING METHODS AND SUBJECT TO FIELD INSPECTION***