Notes:
001. MINIMUM #12 COPPER CONDUCTORS PERMITTED EXCEPT FOR CONTROLS.
002. ONLY ALUMINIM WIRE PERMITTED IS SERVICE ENTRANCE AND FEEDERS 1/0 AND LARGER STABIL-ALLOY SERIES 6000 & 8000.
003. PULL EQUIPMENT GROUNDS IN ALL RACEWAYS.
004. PROVIDE EXIT AND EMERGENCY LIGHTING AS NOTED AND REQUIRED PER 2003 IBC & 2005 NEC.
005. LIGHTING AND CONTROLS SHALL COMPLY WITH 2006 IECC WHERE APPLICABLE.
006. ALL ELECTRICAL INSTALLATIONS WILL BE SUBJECT TO FIELD INSPECTIONS AND INSPECTOR APPROVALS.
007. ELECTRICAL WILL BE DESIGNED AND INSTALLED PER THE 2005 NATIONAL ELECTRICAL CODE WITH LOCAL AMENDMENTS STATED IN CITY OF FRISCO ORDINANCE ALONG WITH THE FOLLOWING COMMENTS.
008. ANY WIRE/CONDUCTORS USED IN HVAC PLENUM AREA SHALL BE PLENUM RATED.
009. ANY POKE-THRU FLOOR OUTLET ASSEMBLIES SHALL BE UL LISTED FIRE/SMOKE PROTECTED.
010. ALL EXTERIOR LIGHTING SHALL COMPLY WITH COMPREHENSIVE ZONING ORDINANCE ARTICLE IV SECTION 6 LIGHTING & GLARE RQ'MENTS.
110. AN AS-BUILT LEGIBLE PANEL SCHEDULE SHALL BE AFFIXED TO THE INSIDE OF ELECTRICAL PANELS FOR EACH TENANT.
220. BATTERY BACK-UP LIGHTING-----------THIS IS MANDATORY LIGHTING FOR ALL EXTERIOR EGRESS/INGRESS POINTS & IN COMMERCIAL RESTROOMS.
277. GROUNDING AND BONDING SHALL COMPLY WITH ARTICLE 250.
480. ARTICLE 110-13 (b) NATURAL COOLING OF EQUIPMENT IS REQ'D. AND SHALL NOT BE OBSTRUCTED. NATURAL VENTILATION MUST COMPLY WITH IMC SECTION 402 AND T.403.1 WITH 0.05 CFM/SQ.FT.
PROVIDE 1 HR. RATED ELECTRICAL OUTLET BOXES IN @ I HR. CORRIDOR AND @ DEMISING WALLS.
THESE ARE GENERAL REQ'MENTS AND CAN BE VERIFIED IN THE FIELD, SOME NOTATIONS WILL NOT BE APPLICABLE BASED ON TYPE OF INSTALLATION.
26989 SQ.FT DEMO HIGH BAY, INSTALL NEW 2X4 HIGH BAY LITES