Short Description:
3945 AC, 4734 SF, SFR / 2 STORY
Expiration Date:
7/6/2018
Notes:
3945 AC, 4734 SF, SFR / 2 STORY
10/15/2015 12:00:00 AM
001. COMPLIANCE WITH THE AMENDED (06/18/13) ZONING ORDINANCE.
002. COMPLIANCE WITH THE 2012 BUILDING CODES, LOCAL AMENDMENTS, PD AND FINAL PLAT REQUIREMENTS.
003. TERMITE BARRIER PROTECTION REQ'D AT ALL SLAB PENETRATIONS.
014. BEAMS=10"W X 28"D.
023. FRONT ENTRY CURB CUT PER ENCLOSED DESIGN SKETCH WITH DRIVEWAY MAXIMUM WIDTH 24 FEET.
027. WINDOW BOX-OUTS WITH SIDING & TRIM MUST NOT EXCEED TWICE THE WINDOW M.O. AREA.
029. PROVIDE EXPANSION JOINTS IN MASONARY FACADE.
032. ALL SIDING, TRIM, SHAKES AND SIMILAR NON-MASONRY EXTERIOR SURFACE COVERINGS MUST BE OF CEMENTITIOUS MATERIAL; (OR) ENGINEERED/TREATED WOOD PRODUCT.
042. TEMPERED GLASS REQ'D AT WINDOWS AND PARTITIONS WITHIN 2' OF DOOR OPENINGS.
043. TEMPERED GLASS REQ'D AT ALL BATHROOM HAZARD LOCATIONS, INCLUDING WINDOWS AND PARTITIONS IF GLAZING IS LESS THAN 60" ABOVE ANY STANDING/WALKING SURFACE.
045. MINIMUM OF 24" ON SILL HEIGHT AT 2ND STORY OPERABLE WINDOWS.
046. SECOND STORY WINDOWS (SIZE & TYPE) MUST INCLUDE HEAD HEIGHT
050. DOUBLE UNDERLAYMENT REQUIRED ON COMPOSITION ROOFS WITH A 4:12 PITCH OR LESS
051. CO DETECTORS REQ'D ON ELECTRICAL LEGEND & ELECTRICAL PLAN. (1) PER FLOOR MINIMUM WITH (1) ON THE AC SIDE OF THE GARAGE DOOR AND OUTSIDE THE VICINITY OF EACH BEDROOM.
058. GREEN BUILDING VENTILATION REQUIREMENT BASED ON ASHARAE 62.2 STANDARD.
059. DRIVEWAY, LEADWALK & GARAGE DOOR ENHANCEMENT & TREATMENT PER THE ENCLOSED
060. THIS SUBDIVISION MAY REQUIRE H.O.A. DESIGN APPROVAL PRIOR TO PERMIT AND CONSTRUCTION.
061. SEE ENCLOSED SHEET FOR WOOD FENCE CONSTRUCTION AND (OR) ORNAMENTAL IRON AS PER PD REQUIREMENT
Parcel Info
City/State/Zip:
FRISCO, TX, 75035
Subdivision:
ARBORS AT WILLOW BAY PHASE IV THE (CFR)
|
BF TESTER | DAVID HERNANDEZ | (972)670-5490 | | 2707 BELHAVEN DR | MESQUITE, TX 75150 |
OWNER | EZHIL ZIVAN & YAMINI KELAPPAN | ()- | | | FRISCO, TX 75035-7164 |
MAIL TO | EZHIL ZIVAN & YAMINI KELAPPAN | ()- | | | FRISCO, TX 75035-7164 |
APPLICANT | DR HORTON | (214)607-4244 | dfweastpermits@drhorton.com | | ROWLETT, TX 75088 |
CONTRACTOR | DR HORTON | (214)607-4244 | dfweastpermits@drhorton.com | | ROWLETT, TX 75088 |
ELECT. CTR. | LANEHART ELECTRIC | (972)721-1004 | dallaslec@lanehart.com | | IRVING, TX 75061 |
HERS PROVIDE | STRAND SYSTEMS ENG INC | (972)620-8204 | jennifer@stransystems.com | | IRVING, TX 75039 |
MECH. CTR. | RELIANT HEATING AND AIR CONDIT | (817)616-1100 | ahinson@reliantac.com | PO BOX 166169 | IRVING, TX 75016 |
PLUM. CONT. | D & M PLUMBING CONTRACTORS | (903)454-3939 | RSMITHDM@GMAIL.COM | | GREENVILLE, TX 75404 |
STRUCT ENG | ERIC L DAVIS ENGINEERING | (972)564-0592 | robp@eldengineering.com | | FORNEY, TX 75126 |
Total Fees |
Charged: $0.00
Balance Due: $0.00
|
There are currently no reviews on this record.