Permit Info
Short Description:
3819 AC, 4306 SF, SFR / 2 STORY
Notes:
3819 AC, 4306 SF, SFR / 2 STORY
4/22/2011 12:00:00 AM
(4/22/2011 10:08 AM JC)
001. ENERGY STAR/GREEN BLDG/90 DAY DIRECTIVE EFF 04/01/2011.
002. COMPLIANCE WITH THE 2006 CODES, AMENDMENTS, ORDINANCES & SUBDIVISION REQUIREMENTS.
003. TERMITE PROTECTION REQ'D AT ALL SLAB PENETRATIONS.
007. BEAMS=8"W X 30"D.
025. TEMPERED GLASS REQ'D AT WINDOWS WITHIN 2' OF DOOR OPENINGS.
029. TEMPERED GLASS AT FLOAT GLASS WINDOWS GREATER THAN 9 SQ FT, LESS THAN 18" OFF FINISH FLOOR, WITHIN 3'-0" OF A WALKING SURFACE.
032. SECOND FLOOR SIDING AREA MUST NOT EXCEED 50% OF THE TOTAL NET EXPOSED WALL AREA.
038. RETAINING WALLS TWO (2) FT OR TALLER MUST BE OF ENGINEERED DESIGN.
042. THIS SUBDIVISION MAY REQUIRE H.O.A. DESIGN APPROVAL PRIOR TO PLAN SUBMITTAL AND CONSTRUCTION.
043. COMPLIANCE WITH E.O.R. FOUNDATION DESIGN NOTE(S) REQ'D. BY BUILDER PRIOR TO THE START OF CONSTRUCTION. COPY SAME TO THE CITY OF FRISCO.
044. CO DETECTORS REQ'D ON ELECTRICAL LEGEND & ELECTRICAL PLAN 1/1000 SQ. FT. & 1 PER FLOOR MINIMUM WITH (1) ON THE AC SIDE OF THE GARAGE DOOR.
046. FRONT ENTRY CURB CUT PER ENCLOSED DESIGN SKETCH.
048. LANDSCAPE IRRIGATION SYSTEM, IF INSTALLED, REQUIRES DESIGN APPROVAL PRIOR TO REQUEST FOR FINAL INSPECTION (CO).
049. GREEN BUILDING VENTILATION REQUIREMENT BASED ON ASHARAE 62.2 STANDARD.
050. ET BASED CONTROLLER REQUIRED FOR AUTOMATIC IRRIGATION SYSTEMS PER CITY ORDINANCE ZA06-0005 DATED 11/24/2006.
054. PROVIDE EXPANSION JOINTS IN MASONARY FACADE.
060. ONLY THE EOR STRUCTURE FRAME AND DETAILS ARE INCLUDED AS PART OF TIHS ISSUED BUILDING PERMIT.
(4/22/2011 10:08 AM JC)
(MFD)
Parcel Info
City/State/Zip:
FRISCO, TX, 75035
Subdivision:
DOMINION AT PANTHER CREEK #4A (CFR)
|
BF TESTER | JAY S. BIRD JR | (972)647-8398 | | 1433 CHISUM TRAIL | WHITESBORO, TX 76273 |
OWNER | GRAND HOMES | (972)387-6037 | LDYE@GRANDHOMES.COM | 15950 N DALLAS PKY #600 | DALLAS, TX 75248 |
APPLICANT | GRAND HOMES | (972)387-6037 | LDYE@GRANDHOMES.COM | 15950 N DALLAS PKY #600 | DALLAS, TX 75248 |
CONTRACTOR | GRAND HOMES | (972)387-6037 | LDYE@GRANDHOMES.COM | 15950 N DALLAS PKY #600 | DALLAS, TX 75248 |
ELECT. CTR. | IES RESIDENTIAL, INC | (972)562-7724 | BECKY.COLLIER@IES-CO.COM | 713 TOWER LANE SUITE A | MCKINNEY, TX 75069 |
HERS PROVIDE | ACP ALLIED CONSTRUCTION PROFES | (214)227-9540 | TONYA@ENERGYACP.COM | 1900 ESPINOSA DRIVE | Carrollton, TX 75010 |
MECH. CTR. | AIRTRON INC | (972)272-9633 | CHERRI.GAINS@RESSERVICES.COM | 9525 FORESTVIEW STREET | DALLAS, TX 75243 |
PLUM. CONT. | TEXAS UNITED PLUMBING | (972)446-2500 | | 1451 HALSEY WAY | CARROLLTON, TX 75007 |
STRUCT ENG | STRAND SYSTEMS ENGINEERING | (972)620-8204 | TAMI@STRANDSYSTEMS.COM | 6221 RIVERSIDE DRIVE #116 | IRVING, TX 75039 |
Total Fees |
Charged: $0.00
Balance Due: $0.00
|
|
BACKFLOW | APPROVED |
10/3/2011
| | 10/3/2011 | |
More Info
|