Notes:
1- CONTINGENT UPON COMPLIANCE TO BLDG CODE & LOCAL REQUIREMENTS, PERTINENT LEGISLATIONS AND REVIEW COMMENTS.
2- BLDG TO FUNCTION AS MULTI-TENANT CRITERIA (EVEN IF OCCUPIED BY ONLY ONE TENANT). EXIT CORRIDOR #200 TO BE MAINTAINED AS 1 HR PARTITIONED EXIT PATHWAY, FROM STAIRS TO 2ND LEVEL LOBBY, WITH RATED DOORS AS REQ'D. (SPACES ENTERED FROM EXIT CORRIDOR ONLY, AND ABLE TO FUNCTION INDEPENDENTLY AS POTENTIAL SUITES, MUST BE SEPARATED BY 1 HR DEMISING WALLS).
3- THE "EXISTING TENANT TO REMAIN" (SPACE #226), MUST BE CONSIDERED A SEPARATED SUITE PROVIDED WITH TWO RECESSED & OUT-SWINGING EXIT CORRIDOR DOORS AS REQ'D AND PART OF THE SCOPE OF WORKS FOR THIS PROJECT.
4- ROOMS, ELECTRICAL #229 AND STORAGE #235, TO BE 1 HR WITH 45 MINUTE DOORS IN 1 HR FRAME. (ELECT'L DOOR MUST, TYPICALLY, SWING OUT).
5- ANY FLOOR OUTLET MUST BE BY CORE-DRILLING & RATED POKE-THRU INSTALLATION AS PER APPROVED UL-LISTED DEVICE. (PROVIDE FLOOR PATCHING OF ANY ABANDONED CORE-DRILLING). ANY WOOD, SUCH AS PLYWOOD BACKBOARDS, MUST BE FIRE-RETARDANT-TREATED WOOD.
6- SUBJECT TO M.E.P. REVIEWS, FIRE MARSHAL AND FIELD INSPECTIONS.
WARNING:
BECAUSE NO COPIES OF REVIEW-MARKED DWGS ARE KEPT BY THE CITY, OWNER, OWNER'S REPRESENTATIVE, AND/OR CONTRACTORS, ARE RESPONSIBLE FOR PRINTING THEIR OWN RECORDS AND MUST BE ABLE TO PROVIDE A REPLACEMENT COPY IN CASE ANY RELEASED MARKED DWG OR PERMIT SET IS LOST, DAMAGED, UNAVAILABLE AT THE JOB SITE OR WHEN RECALLED BY BLDG OFFICIAL. OTHERWISE, CONSTR'N MAY NOT PROCEED UNTIL DWGS ARE RESUBMITTED FOR NEW REVIEW AND ALL RELATED FEES ARE PAID.
1 BF (removed) - CONIFER (G3)