Notes:
7/17/2020 1:25:42 PM
Fireplace
1- All work performed must meet the 2018 IRC standards.
2- Venting and flue must meet manufacturers specifications. Must maintain clearances per R1001.11 2015 IRC.
3- Chimney must maintain a minimum of 2' clearance (excluding spark arrestor) in height within a 10' radius of chimney.
4- Footer thickness 12" min & width 6" each side of fireplace wall.
5- 100% masonry structure, no greater than 8 ft may encroach into the rear yard up to 10 ft from property line.
6- May not intrude on side yard setback. Exception: May encroach up to 7 ft on corner lots.
7- A gasoline pressure test is required when adding gas to an outdoor fireplace.
8- Subject to field inspection approval. Call (972) 292-5386 for inspection.
9- City of Frisco approval is not in lieu of homeowner association HOA requirements. Reference HOA bylaws for subdivision requirements.
Grill Area
1- All work performed must meet the 2018 IRC standards and abide by the City of Frisco comprehensive Zoning Ordinance, and all other city Ordinances.
2- May not intrude on side yard setbacks. exception: may encroach up to 7 ft on corner lots.
3- A gas line pressure test is required when adding gas to an outdoor appliance.
4- Subject to field inspection approval. call (972) 292-5386 for inspection.
5- Must be 3’ from side property line once past rear build line. must be 10’ from rear property line.
6- City of Frisco approval is not in lieu of homeowner association HOA requirements. Reference HOA bylaws for subdivision requirements.