Notes:
10/2/2019 1:48:55 PM
01. Conductors smaller than #12 AWG not permitted.
02. No aluminum conductors permitted.
03. PV installations shall comply with article 690, 2014 National Electrical Code.
04. All installations are subject to field inspection and approval. Call (972) 292-5386 for inspection.
05. PULL EQUIPMENT GROUNDS IN ALL RACEWAYS.
ELECTRICAL WILL BE DESIGNED AND INSTALLED PER THE 2014 NATIONAL ELECTRICAL CODE WITH LOCAL AMENDMENTS STATED IN CITY OF FRISCO ORDINANCE 16-12-101 ALONG WITH THE FOLLOWING COMMENTS.
06. * ALL WORK PERFORMED MUST MEET THE 2015 IRC STANDARDS AND ABIDE BY THE CITY OF FRISCO COMPREHENSIVE ZONING ORDINANCE, AND ALL OTHER CITY ORDINANCES.
07. CITY OF FRISCO APPROVAL IS NOT IN LIEU OF HOMEOWNER ASSOCIATION (HOA) REQUIREMENTS. REFERENCE HOA BYLAWS FOR SUBDIVISION REQUIREMENTS.
08. SUBJECT TO FIELD INSPECTION APPROVAL. CALL (972) 292-5386 FOR INSPECTION.