Notes:
1/31/2019 5:49:35 PM
A RESIDENTIAL DRIVEWAY FLARE LOCATED UPSTREAM SHOULD BE NO CLOSER THAN FIFTEEN FEET FROM THE CURB RETURN OF THE UPSTREAM INTERSECTION AND A DOWNSTREAM FLARE NO CLOSER THAN FIVE FEET FROM THE CURB RETURN OF A DOWNSTREAM INTERSECTION.
IMPERMEABLE SURFACE AREA SHALL NOT EXCEED 50% OF THE AREA BETWEEN THE PROPERTY LINE AND THE BUILDING LINE.
1/31/2019 5:51:17 PM
001. COMPLIANCE WITH THE AMENDED ZONING ORDINANCE (13-06-36) AND ALL DEED RESTRICTIONS SHOWN ON THE FINAL PLAT (DRIVEWAY; FENCE).
002. COMPLIANCE WITH THE 2015 BUILDING CODES, LOCAL AMENDMENTS, PD AND FINAL PLAT REQUIREMENTS.
003. TERMITE BARRIER PROTECTION REQ'D AT ALL SLAB PENETRATIONS.
004. DRIVEWAY SLOPE MUST NOT EXCEED 12%; PLOT PLANS WITH SPOT GRADES ARE REQUIRED.
007. MAX SIDEWALK SLOPE IS 8.3%, ADD STEPS AS REQ'D.
016. BEAMS=10"W X 30"D.
023. FRONT ENTRY CURB CUT PER ENCLOSED DESIGN SKETCH WITH DRIVEWAY MAXIMUM WIDTH 24 FEET.
029. PROVIDE EXPANSION JOINTS IN MASONARY FACADE.
034. RESIDENTIAL STUCCO REQUIRES LATH AND EXPANDED WIRE MESH WITH CEMENT PLASTER.
037. ATTIC STORAGE MUST NOT BE CONVERTED TO HABITABLE LIVING AREA WITHOUT A BUILDING PERMIT
041. TEMPERED GLASS REQUIRED AT WINDOWS ADJACENT TO STAIRS
042. TEMPERED GLASS REQUIRED AT WINDOWS AND PARTITIONS WITHIN 2' OF DOOR OPENINGS.
043. TEMPERED GLASS REQUIRED AT ALL BATHROOM HAZARD LOCATIONS, INCLUDING WINDOWS AND PARTITIONS IF GLAZING IS LESS THAN 60" ABOVE ANY STANDING/WALKING SURFACE.
044. TEMPERED GLASS AT FLOAT GLASS WINDOWS GREATER THAN 9 SQ FT, LESS THAN 18" OFF FINISH FLOOR, WITHIN 3'-0" OF A WALKING SURFACE.
045. MINIMUM OF 24" ON SILL HEIGHT AT 2ND STORY OPERABLE WINDOWS. EMERGENCY/ESCAPE RESCUE OPENINGS SHALL HAVE NET CLEAR OPENING OF 5.7 SF. MINIMUM NET CLEAR HEIGHT OF 24" AND NET CLEAR WIDTH OF 20" (GRADE FLOOR OR BELOW 5.0 SF).
048. MEDIA ROOM WITH CLOTHING STORAGE MUST HAVE A CODE COMPLIANT EGRESS WINDOW.
052. AUTOMATIC FIRE SPRINKLERS REQ'D W/ DESIGN AND INSTALLATION APPROVED BY FIRE MARSHAL.
061. SEE ENCLOSED SHEET FOR WOOD FENCE CONSTRUCTION AND (OR) ORNAMENTAL IRON AS PER PD REQUIREMENT.
060. THIS SUBDIVISION MAY REQUIRE H.O.A. DESIGN APPROVAL PRIOR TO PERMIT AND CONSTRUCTION.
059. DRIVEWAY, LEADWALK AND GARAGE DOOR ENHANCEMENTAND TREATMENT PER THE ENCLOSED