Notes:
5958 SQ FT, CIFO / VENUS EXPRESSION ACADEMY
5/15/2013 12:00:00 AM
CONTINGENT UPON COMPLIANCE WITH REVIEW COMMENTS, CODE REQUIREMENT AND PERTINENT LEGISLATIONS. REFERENCE APPROVED REDLINES PLANS AND PLAN REVIEW HISTORY DOCUMENT FOR ANY & ALL PLAN REVIEW COMMENTS.
ALL WORK PERFORMED MUST MEET THE 2006 IBC, IMC, IPC, IFC, 2009 IECC & 2005 NEC STANDARDS, ABIDE BY THE CITY OF FRISCO ZONING ORDINANCE (11-04-09) AND ALL OTHER CITY ORDINANCES AND LOCAL AMENDMENTS .
SUBJECT TO M.E.P. & FIRE MARSHAL REVIEWS AND FIELD INSPECTIONS. CALL (972) 292-5386 FOR INSPECTION.
ALL SUBCONTRACTORS MUST VALIDATE AND OBTAIN CURRENT REGISTRATION WITH THE CITY PRIOR TO START OF PROJECT.
(6/12/2013 10:50 AM SLC)
ELECTRICAL PLANS APPROVED WITH RISER DIAGRAM ONLY. PRIOR TO ROUGH INSPECTION, ELECTRICIAN SHALL SUPPLY PANEL SCHEDULE AND LOAD CALCULATIONS.
ALL CONDUCTORS SHALL BE IN EMT CONDUIT OR MC CABLE, SHALL BE MINIMUM #12 AWG COPPER.
COORDINATE WITH INSPECTOR FOR EMERGENCY EGRESS LIGHTING AND EXIT SIGN LOCATIONS.
(6/12/2013 10:54 AM SLC)
PLUMBING RISER DIAGRAMS ACCEPTED.
PRIOR TO ROUGH INSPECTION, PLUMBER SHALL PROVIDE PLUMBING FLOOR PLAN.
(6/12/2013 10:58 AM SLC)
MECHANICAL DUCT PLAN ACCEPTED. PRIOR TO ROUGH INSPECTION, MANUAL D CALCULATIONS FOR DUCT SIZING SHALL BE SUBMITTED TO INSPECTOR.
(6/12/2013 11:54 AM SLC)
FIRE SUPPRESSION AND ALARM PERMITS SHALL BE COORDINATED THROUGH THE FIRE MARSHAL'S OFFICE. CONTACT # 972 292-6300.