Notes:
200 SQ FT, SALT / CONCRETE, GRILL AREA & FIREPLACE
9/20/2012 12:00:00 AM
102. * ALL WORK PERFORMED MUST MEET THE 2006 IRC STANDARDS AND ABIDE BY THE CITY OF FRISCO COMPREHENSIVE ZONING ORDINANCE, AND ALL OTHER CITY ORDINANCES.
105. *** NEED A FLATWORK INSPECTION BEFORE THE POUR. ***
147. *** FIRE PIT NOT REQUESTED OR PERMITTED. ***
175. * FIREPLACE MUST BE 100% MASONRY.
176. * VENTING AND FLUE MUST MEET MANUFACTURERS SPECIFICATIONS.
177. * MUST MAINTAIN TEN FOOT CLEARANCE FROM ALL COMBUSTABLE ITEMS.
178. * CHIMNEY MUST MAINTAIN A MINIMUM OF 2' IN CLEARANCE (EXCLUDING SPARK ARRESTOR) IN HEIGHT WITHIN A 10' RADIUS OF CHIMNEY.
179. * FOOTER THICKNESS 12" MIN & WIDTH 6" EACH SIDE OF FIREPLACE WALL.
103. SUBJECT TO FIELD INSPECTION APPROVAL. CALL (972) 292-5386 FOR INSPECTION.