Permit Info
Short Description:
COMM, ANTENNA INSTALL / CLEAR WIRELESS
Expiration Date:
12/29/2010
Notes:
COMM, ANTENNA INSTALL / CLEAR WIRELESS
7/20/2010 12:00:00 AM
1. ALL WORK TO CONFORM TO SECTION 1609 2006 IBC, LOCAL CODES AND AMENDMENTS.
2. ALL PHASES OF WORK SHALL BE INSPECTED.
3. A NEW SUBSTANTIALLY CONFORMING SITE PLAN MUST BE SUBMITTED TO THE CITY OF FRISCO PLANNING DEPT. ATTENTION LEESA KAM.
(7/12/2010 9:11 AM JM)
Electrical Ordinance 08-01-10
THESE ARE GENERAL NOTES; ITEMS CAN BE VERIFIED IN THE FIELD.
ARTICLE 800, 820, 830 OF THE 2005 NEC SHALL APPLY
1. A. MINIMUM #12 COPPER CONDUCTORS PERMITTED EXCEPT FOR CONTROLS.
B. PROVIDE GFCI PROTECTION FOR ALL 15 AND 20 AMP 120 VOLT KITCHEN OUTLETS.
3. ONLY ALUMINIM WIRE PERMITTED IS SERVICE ENTRANCE AND FEEDERS 1/0 AND LARGER STABIL-ALLOY SERIES 6000 & 8000.
4. PULL EQUIPMENT GROUNDS IN ALL RACEWAYS UNLESS SPECIFIED CONDUIT ON INSTALLATION WILL ACT AS GROUNDING PATH.
7. ALL ELECTRICAL INSTALLATIONS WILL BE SUBJECT TO FIELD INSPECTIONS AND INSPECTOR APPROVALS.
8. ELECTRICAL WILL BE DESIGNED AND INSTALLED PER THE 2005 NATIONAL ELECTRICAL CODE WITH LOCAL AMENDMENTS STATED IN CITY OF FRISCO ORDINANCE ALONG WITH THE FOLLOWING COMMENTS.
11. AN AS-BUILT LEGIBLE PANEL SCHEDULE SHALL BE AFFIXED TO THE INSIDE OF ELECTRICAL PANELS.
13. GROUNDING AND BONDING SHALL COMPLY WITH ARTICLE 250.
BLDG. STRUCTURAL STEEL, GROUND ROD, COPPER DOMESTIC COLD WATER PIPE (UFER IF AVAILABLE PER 250-81)
14. RECOMMENDATION---ARTICLE 110-13 (b) NATURAL COOLING OF EQUIPMENT IS REQ’D. AND SHALL NOT BE OBSTRUCTED.
17. MAINTAIN PROPER WORKING CLEARANCES IN MECHANICAL/ELECTRICAL ROOM ARTICLE 110-26.
Parcel Info
City/State/Zip:
FRISCO, TX, 75034
|
| APPLICANT | CLEAR WIRELESS | (469)223-4609 | brandon.ruez@vcigroupinc.com | 4724 LARGO DRIVE | FLOWER MOUND, TX |
| OWNER | T-MOBILE | (972)464-3708 | | 7668 WARREN PARKWAY | FRISCO, TX 75034 |
| CONTRACTOR | TBD | ()- | | | |
| ELECT. CTR. | CLEAR WIRELESS, LLC-NOT REG | (425)216-7600 | | 4400 CASILLION POINT | KIRKLAND, WA 98033 |
| MECH. CTR. | N/A | ()- | | | |
| PLUM. CONT. | N/A | ()- | | | |
|
| BUILDING PERMIT FEE |
$321.25
|
|
| PLAN REVIEW FEE |
$50.00
|
|
| Total Fees |
|
Charged: $371.25
Balance Due: $371.25
|
There are currently no inspections on this record.
|
| COMMERCIAL REVIEW | Jeff Maxwell | Denied | 7/9/2010 | 7/12/2010 | 8/7/2010 |
More Info
|
| ELECTRICAL REVIEW | Jeff Maxwell | Appd w/ Conditions | 7/9/2010 | 7/12/2010 | 7/12/2010 |
More Info
|
| INITIAL REVIEW | Sharon Elliott | Denied | 7/9/2010 | 7/9/2010 | 7/9/2010 |
More Info
|
| COMMERCIAL REVIEW | Jeff Maxwell | Pending | 7/14/2010 | 7/20/2010 | 8/12/2010 |
More Info
|
| MISC REVIEW | Sharon Elliott | N/A | 7/14/2010 | 7/14/2010 | 7/14/2010 |
More Info
|
| MISC REVIEW | Sharon Elliott | N/A | 8/13/2010 | 8/13/2010 | 8/13/2010 |
More Info
|
| MISC REVIEW | Michele Wood | Pending | 10/6/2010 | 10/6/2010 | |
More Info
|
| MISC REVIEW | Michele Wood | Denied | 12/29/2010 | 12/29/2010 | |
More Info
|