Notes:
INSTALL VENTLESS F/P SALT /
7/13/2010 12:00:00 AM
*******************************************
1. THESE ITEMS LISTED BELOW ARE REQ'D. **********************************
A. THERE MUST BE AN OPERABLE WINDOW IN THE SAME ROOM WHERE THIS APPLIANCE IS INSTALLED. THE WINDOW MUST BE OPENED WHEN THIS APPLIANCE IS OPERATED.
B. THERE MUST BE COMBUSTION AIR PROVIDED THRU A DUCT INSTALLED AT THE APPLIANCE TO PENETRATE EXTERIOR WALL............NO EXCEPTIONS.
C. THIS IS AN UNUSUALLY TIGHT CONSTRUCTED HOME. BASED ON THIS; THE INSTALLATION SHALL COMPLY WITH 2006 IMC.
D. CARBON MONOXIDE DETECTOR MUST BE INSTALLED IN THIS ROOM HARD WIRED IN TO EXISTING DETECTORS.
E. THIS APPLIANCE MUST BE SECURED TO STUD WALL NOT FREESTANDING.
F. INSTALL A CEILING FAN IN THIS ROOM. ************************************
2. UNIT SHALL BE UL 1482 RATED.
3. I HAVE PROVIDED CALCULATIONS ON PLANS TO COMPLY WITH IMC.