Notes:
308 SQ FT, CADD / LONESTAR RANCH AMENITY SHADE COVER
5/17/2010 12:00:00 AM
1. RECOMMENDATION: WOOD CHIPS HAVE BEEN KNOWN TO BE COMBUSTIBLE IN EXTREME HEAT, BE AWARE OF SAFETY FACTORS.
2. PER ATTACHED DOCUMENT: AWNING FABRIC SHALL BE FIRE-RETARDENT. (THIS IS FILED WITH THE City of Frisco)
3. SUBJECT TO FIELD APPROVED INSPECTIONS AND TESTING.
4. PIER INSPECTION IS REQ'D.
5. CONSTRUCTION SHALL COMPLY WITH MANUFACTURERS INSTRUCTIONS AND WITH 2006 IBC SECTION 16 AND SECTION 31. 1607.11.2.4 AWNINGS AND CANOPIES SHALL BE DESIGNED FOR A UNIFORM LOAD OF 5 PSF ROOF LOAD MINIMUM.
6. WIND DESIGN LOAD CATEGORY: 90 MPH 3 SEC. GUST, SEISMIC DESIGN CATEGORY B. EXPOSURE C. SECTION 1609 WIND LOADS
(LATERAL FORCES) NOT LESS THAN 10 PSF.
(5/18/2010 11:44 AM MBW)
CONTINGENT UPON COMPLIANCE WITH REVIEW COMMENTS, CODE REQUIREMENT AND PERTINENT LEGISLATIONS. REFERENCE APPROVED REDLINES PLANS AND PLAN REVIEW HISTORY DOCUMENT FOR ANY & ALL PLAN REVIEW COMMENTS.
ALL WORK PERFORMED MUST MEET THE 2006 IBC, IMC, IPC, IECC, IFC & 2005 NEC STANDARDS, ABIDE BY THE CITY OF FRISCO COMPREHENSIVE ZONING ORDINANCE AND ALL OTHER CITY ORDINANCES AND LOCAL AMENDMENTS .
SUBJECT TO M.E.P. & FIRE MARSHAL REVIEWS AND FIELD INSPECTIONS. CALL (972) 292-5386 FOR INSPECTION.
ALL SUBCONTRACTORS MUST VALIDATE AND OBTAIN CURRENT REGISTRATION WITH THE CITY PRIOR TO START OF PROJECT.
***ISSUANCE OF BUILDING PERMIT DOES NOT INCLUDE FIRE MARSHAL APPROVAL. SEPARATE SUBMITTAL FOR FIRE MARSHAL REVIEW, FIRE SPRINKLER, FIRE ALARM, FIRE UNDERGROUND, AND /OR ANY ADDITIONAL REQUIREMENTS AS SET FORTH BY THE FIRE DEPARTMENT NEED TO BE SUBMITTED DIRECTLY TO THE FIRE MARSHAL OFFICE FOR APPROVAL.***