Notes:
110 SQ FT, SADD / ADD MUD ROOM
2/15/2010 12:00:00 AM
1. MUDD ROOM ALTERATION/ADDITION.
2. UV RATING FOR WINDOW IS .65 AND THE SHGC IS .40 IECC 2006.
3. TREATED SILL PLATE IS REQ'D. WITH 1/2" X 7" KWIK BOLT CONCRETE ANCHORS.
4. FOAM SEAL ALL OF THE SILL PLATE.
5. R-13 WALL AND R-30 CEILING INSULATION IS RQ'D.
6. SUBJECT TO FIELD APPROVED INSPECTIONS.
7. SMOKE DETECTOR IS REQ'D. IT MUST BE HARD WIRED IN TO EXISITNG SMOKE/CARBON DETECTORS.
8. SELF-CLOSING HINGES REQ'D. AT ENTRY DOOR FROM GARAGE TO MUDD ROOM.
9. FYI------EXISTING CKTS TO THIS ROOM ARE MOST LIKELY GFCI CKTS.
10. NO ADDITIONAL PLUMBING IS SHOWN ON THE PLANS.
11. EXISTING TOTAL UNDER ROOF SQ.FT. 5669 PLUS 110 SQ. FT MUDD ROOM =5779.