Notes:
THESE REQ'MENTS WILL BE FIELD VERIFIED.
B09-2128
OCCUPANT LOAD 29
A. CONTINGENT UPON COMPLIANCE WITH BLDG CODES & LOCAL REQUIREMENTS, PERTINENT LEGISLATIONS AND REVIEW COMMENTS.
B. ALL PARTS OF THE BLDG ENVELOPE MUST MATCH OR EXCEED THE MIN. INSULATION REQUIREMENTS OF IECC, WITH R-13 FOR WALLS, R-19 FOR ROOF.
C. SUBJECT TO M.E.P. REVIEWS, FIRE MARSHAL AND FIELD INSPECTIONS.
ALL SUBCONTRACTORS MUST VALIDATE AND OBTAIN CURRENT REGISTRATION WITH THE CITY PRIOR TO START OF PROJECT.
D. TEMPERED WINDOWS/GLASS WHERE APPLICABLE.
E. FULLY SPRINKLED.
F. INTERIOR FINISHES: GROUP-- B CLASS--B
FLAME SPREAD ------------ 25 TO 76
SMOKE DEVELOPED------- 0 TO 450
G. DEMISING WALLS SHALL BE RATED 1 HR. FIRE SMOKE CONSTRUCTION, ALL PENETRATIONS THRU DEMISING WALLS SHALL BE FIRE CAULKED FLOOR TO ROOF DECK.
H. ANY DUCT PENETRATIONS THRU DEMISING WALLS SHALL HAVE FIRE/SMOKE DAMPERS INSTALLED-EXPANDING CAULK PROHIBITED.
I. ALL WOOD BLOCKING SUPPORTING MILLWORK, STANDARDS & EQUIPMENT SHALL BE (FRT) FIRE TREATED WOOD.
J. WHERE ABOVE CEILING AREA IS USED AS HVAC PLENUM-ALL WIRING SHALL BE PLENUM RATED.
L. MILLWORK TO MEET ADA/TAS REQUIREMENTS.
2893 SQ FT, CIFO / TOWN SQUARE FINANCIAL