Notes:
THESE REQ'MENTS WILL BE FIELD VERIFIED.
ICC A117.1 RESTROOM ACCESSIBILITY CLEARANCE SHALL BE 60" X 56" VOID OF ANY ENCROACHMENT IN THE SPACE OF THE W/C {RESTROOM SPACES MUST MEET CURRENT ADA AND TAS & ICC A117}.
A. CONTINGENT UPON COMPLIANCE WITH BLDG CODES & LOCAL REQUIREMENTS, PERTINENT LEGISLATIONS AND REVIEW COMMENTS.
B. ALL PARTS OF THE BLDG ENVELOPE MUST MATCH OR EXCEED THE MIN. INSULATION REQUIREMENTS OF IECC, WITH R-13 FOR WALLS, R-19 FOR ROOF.
C. SUBJECT TO M.E.P. REVIEWS, FIRE MARSHAL AND FIELD INSPECTIONS.
ALL SUBCONTRACTORS MUST VALIDATE AND OBTAIN CURRENT REGISTRATION WITH THE CITY PRIOR TO START OF PROJECT.
D. TEMPERED WINDOWS/GLASS WHERE APPLICABLE.
F. INTERIOR FINISHES: GROUP-- B CLASS--C
FLAME SPREAD ------------ 76 TO 100
SMOKE DEVELOPED------- 0 TO 450
H. ANY DUCT PENETRATIONS THRU DEMISING WALLS SHALL HAVE FIRE/SMOKE DAMPERS INSTALLED-EXPANDING CAULK PROHIBITED.
I. ALL WOOD BLOCKING SUPPORTING MILLWORK, STANDARDS & EQUIPMENT SHALL BE (FRT) FIRE TREATED WOOD.
J. WHERE ABOVE CEILING AREA IS USED AS HVAC PLENUM-ALL WIRING SHALL BE PLENUM RATED.
K. CONTRACTOR TO VERIFY FIRE RISER ROOM LOCATION. THERE SHALL BE ACCESS TO THE CENTRALLY LOCATED OR INDIVIDUALLY LOCATED FIRE RISER ROOM. WHERE RTU'S ARE APPLICABLE THERE SHALL BE SAME FOR ACCESS TO THIS EQUIPMENT. (WHERE INSTALLED, ROOF HATCH ACCESS SHALL BE FIRE SMOKE SEALED).
L. MILLWORK TO MEET ADA/TAS REQUIREMENTS.
3880 SQ FT, CALT / CHASE BANK