Notes:
CNEW / SORANO LIFT STATION
3/3/2008 12:00:00 AM
PERMIT IS FOR RESIDENTIAL LIFT STATION ONLY. ALL OTHER STRUCTURES TO BE PERMITTED SEPERATELY.
A. CONTINGENT UPON COMPLIANCE WITH BLDG CODES & LOCAL REQUIREMENTS, PERTINENT LEGISLATIONS AND REVIEW COMMENTS.
B. TYVEK AND LATHE MUST BE APPLIED TO OSB AND/OR PLYWOOD SHEATHING PRIOR TO APPLICATION OF STUCCO. SHEATHING AND LATHE INSPECTIONS ARE REQUIRED.
C. ALL WORK SUBJECT TO FIELD INSPECTIONS AND TESTING.
001. MINIMUM #12 COPPER CONDUCTORS PERMITTED EXCEPT FOR CONTROLS.
002. ONLY ALUMINIM WIRE PERMITTED IS SERVICE ENTRANCE AND FEEDERS 1/0 AND LARGER STABIL-ALLOY SERIES 6000 & 8000.
003. PULL EQUIPMENT GROUNDS IN ALL RACEWAYS.
004. PROVIDE EXIT AND EMERGENCY LIGHTING AS NOTED AND REQUIRED PER 2003 IBC & 1999 NEC.
005. LIGHTING AND CONTROLS SHALL COMPLY WITH 2000 IECC WHERE APPLICABLE.
006. ALL ELECTRICAL INSTALLATIONS WILL BE SUBJECT TO FIELD INSPECTIONS AND INSPECTOR APPROVALS.
007. ELECTRICAL WILL BE DESIGNED AND INSTALLED PER THE 1999 NATIONAL ELECTRICAL CODE WITH LOCAL AMENDMENTS STATED IN CITY OF FRISCO ORDINANCE 00-03-02 ALONG WITH THE FOLLOWING COMMENTS.
008. ANY WIRE/CONDUCTORS USED IN HVAC PLENUM AREA SHALL BE PLENUM RATED.
009. ANY POKE-THRU FLOOR OUTLET ASSEMBLIES SHALL BE UL LISTED FIRE/SMOKE PROTECTED.
110. AN AS-BUILT LEGIBLE PANEL SCHEDULE SHALL BE AFFIXED TO THE INSIDE OF ELECTRICAL PANELS FOR EACH TENANT.
220. BATTERY BACK-UP LIGHTING-----------THIS IS MANDATORY LIGHTING FOR ALL EXTERIOR EGRESS/INGRESS POINTS & IN COMMERCIAL RESTROOMS.
277. GROUNDING AND BONDING SHALL COMPLY WITH ARTICLE 250.
480. ARTICLE 110-13 (b) NATURAL COOLING OF EQUIPMENT IS REQ'D. AND SHALL NOT BE OBSTRUCTED. NATURAL VENTILATION MUST COMPLY WITH IMC SECTION 402 AND T.403.1 WITH 0.05 CFM/SQ.FT.