Notes:
2415 SQ FT, CIFO / DEL MAR ENERGY
11/7/2007 12:00:00 AM
A.) CONNECTION OF 1-HOUR FIRE RATED DEMISING WALL SHALL BE TO A MULLION AND SHALL BE FIRE/SMOKE SEALED ON BOTH SIDES OF THE WALL.
B.) TENANTS SHALL BE SEPARATED BY AT LEAST 1-HOUR FIRE RATED DEMISING WALL FROM FLOOR TO ROOF/DECK ABOVE.
C.) ANY NEW WALL PATCHWORK OR NEW PARTITION ALONG RATED EXIT ACCES CORRIDOR/HALLWAY MUST BE RATED TO MATCH EXISTING (MIN. 1 HR UL-U465), UP TO UNDERSIDE OF DECK ABOVE (AS APPLICABLE), FULLY FIRE SEALED ON BOTH SIDES AND WITH PROTECTED OPENINGS AS REQ'D. FIRE/SMOKE COMBINATION DAMPERS MUST BE ADDED, OR RELOCATED, AT ANY NEW POINT OF DUCTWORK'S RATED PENETRATIONS & AS ACCEPTABLE TO INSPECTORS.
D.) PROVIDE EXIT LIGHTS AS MARKED ON PLANS AS PER 2003 IBC 1006.1.
E.) EXISTING STRUCT'L FIREPROOFING (EITHER SPRAY-ON OR GYP BD TYPE), WHICH IS AFFECTED OR DAMAGED BY ALTERATION WORK, MUST BE FULLY RESTORED OR REFURBISHED TO MAINTAIN THE INTEGRITY OF STRUCTURE'S ORIGINAL RATING (BUT NOT LESS THAN REQUIRED RATING), ACCORDING TO MIN. TYPE OF CONSTR'N & TO UL-LISTED DESIGNS AS REQ'D.
F.) ANY WOODS USED IN A TYPE II-A CONSTRUCTION SHALL BE OF FIRE RETARDANT TREATED WOOD.
G.) MEMBRANE PENETRATIONS SHALL NOT REDUCE THE 1-HOUR FIRE RESISTANCE RATING OF THE WALL.
H.) NO WORK IS ALLOWED TO BE ADDED TO, OR MODIFIED FROM, WHAT SHOWN IN PERMIT SET, UNLESS FOLLOW-UP REVISIONS ARE SUBMITTED AND APPROVED AS REQ'D.
I.) ACCEPTABILITY OF USE, LAYOUT AND TYPE OF CONSTR'N OF NEWLY CREATED SPACES (NOT IDENTIFIED ON PLANS) SUBJECT TO INSPECTOR'S VERIFICATION & APPROVALS.
J.) SAFETY GLAZING AS REQUIRED IN IBC 2406.
K.) FIRE RATED POKE THRU DEVICES REQUIRED (PROVIDE FLOOR PATCHING OF ANY ABANDONED CORE DRILLING).
L.) COMBINATION FIRE/SMOKE DAMPERS REQUIRED ON ALL DUCTS AND AIR TRANSFER OPENINGS THAT PENETRATES A RATED CONSTRUCTION.
M.) SUBJECT TO ADDITIONAL REQUIREMENTS FROM M.E.P. REVIEWS, FIRE MARSHAL AND FIELD INSPECTIONS.