Notes:
2827 SQ FT, CIFO / ENTERPRISE STAFFING
8/14/2007 12:00:00 AM
1. ALL WORK SUBJECT TO FIELD APPROVED INSPECTIONS AND TESTING.
2. ANY WOOD SHALL BE FIRE TREATED/RETARDENT.
3. FULLY SPRINKLED.
4. DEMISING WALLS--UL U465.
(8/13/2007 06:19 GLQ)
1. MINIMUM #12 COPPER CONDUCTORS PERMITTED EXCEPT FOR CONTROLS.
2. NO ALUMINIM WIRE PERMITTED.(FEEDERS PERMITTED 1/0 AND ABOVE)
3. PULL EQUIPMENT GROUNDS IN ALL RACEWAYS.
4. PROVIDE EXIT AND EMERGENCY LIGHTING AS NOTED AND REQUIRED PER 2000 IBC.
5. LIGHTING AND CONTROLS SHALL COMPLY WITH 2000 IECC WHERE APPLICABLE.
6. ALL CONDUCTORS MUST TERMINATE IN DEVICES THAT HAVE BEEN PROPERLY TIGHTENED TO MANUFACTURE'S TORQUE SPECIFICATIONS. USING THE PROPER TORQUE TOOL.
ALL ELECTRICAL INSTALLATIONS WILL BE SUBJECT TO FIELD INSPECTIONS AND INSPECTOR APPROVALS.
ELECTRICAL WILL BE DESIGNED AND INSTALLED PER THE 1999 NATIONAL ELECTRICAL CODE WITH LOCAL AMENDMENTS STATED IN CITY OF FRISCO ORDINANCE 00-03-02 ALONG WITH THE FOLLOWING COMMENTS.