900 SQ FT, CALT / CELEBRATION COVENANT CHURCH REMODEL
8/7/2007 12:00:00 AM
1. CONTINGENT UPON COMPLIANCE TO BLDG CODE & LOCAL REQUIREMENTS, PERTINENT LEGISLATIONS AND REVIEW COMMENTS.
2. ANY NEW WALL PATCHWORK OR NEW PARTITION ALONG RATED EXIT CORRIDOR AND DEMISING MUST BE RATED TO MATCH EXISTING (MIN. 1 HR UL-U465), UP TO UNDERSIDE OF DECK ABOVE (AS APPLICABLE), FULLY FIRE SEALED ON BOTH SIDES AND WITH PROTECTED OPENINGS AS REQ'D. FIRE/SMOKE COMBINATION DAMPERS MUST BE ADDED, OR RELOCATED, AT ANY NEW POINT OF DUCTWORK'S RATED PENETRATIONS & AS ACCEPTABLE TO INSPECTORS.
3. EXISTING STRUCT'L FIREPROOFING (EITHER SPRAY-ON OR GYP BD TYPE), WHICH IS AFFECTED OR DAMAGED BY ALTERATION WORK, MUST BE FULLY RESTORED OR REFURBISHED TO MAINTAIN THE INTEGRITY OF STRUCTURE'S ORIGINAL RATING (BUT NOT LESS THAN REQUIRED RATING), ACCORDING TO MIN. TYPE OF CONSTR'N & TO UL-LISTED DESIGNS AS REQ'D.
4. ANY WOODS USED IN A TYPE II-A CONSTRUCTION SHALL BE OF FIRE RETARDANT TREATED WOOD.
5. MEMBRANE PENETRATIONS SHALL NOT REDUCE THE 1-HOUR FIRE RESISTANCE RATING OF THE WALL.
6. NO WORK IS ALLOWED TO BE ADDED TO, OR MODIFIED FROM, WHAT SHOWN IN PERMIT SET, UNLESS FOLLOW-UP REVISIONS ARE SUBMITTED AND APPROVED AS REQ'D.
7. ACCEPTABILITY OF USE, LAYOUT AND TYPE OF CONSTR'N OF NEWLY CREATED SPACES (NOT IDENTIFIED ON PLANS) SUBJECT TO INSPECTOR'S VERIFICATION & APPROVALS.
8. SAFETY GLAZING AS REQUIRED IN IBC 2406.
9. MANUEVERING CLEARANCE IN DOOR GOING INTO THE WOMEN'S RESTROOM SHALL BE AT LEAST 18" FROM THE EDGE OF THE DOOR TO THE WALL.
10. DOOR 101, 102 AND ITS VISION PANEL ASSEMBLY SHALL BE PROTECTED AS FOLLOWS; DOOR = 20 MINUTES RATING, GLASS = 45 MINUTES RATING, AND FRAME = 1-HOUR RATING.
11. SUBJECT TO ADDITIONAL REQUIREMENTS FROM M.E.P. REVIEWS, FIRE MARSHAL AND FIELD INSPECTIONS.