PLAN REVIEW COMMENTS;
1. OFFICES 102, 103, 104, AND 106 SHALL HAVE MANUEVERING CLEARANCE OF 12 INCHES MINIMUM FOR DOOR WITH A FRONT/ PUSH SIDE APPROACH. SUBMIT REVISED PLANS OR COMPLY AS MARKED IN THE DRAWINGS.
2. CONTINGENT UPON COMPLIANCE TO BLDG CODE & LOCAL REQUIREMENTS, PERTINENT LEGISLATIONS AND REVIEW COMMENTS.
3. ANY NEW WALL PATCHWORK OR NEW PARTITION ALONG RATED WALL CONSTRUCTION MUST BE RATED TO MATCH EXISTING (MIN. 1 HR UL-U465), UP TO UNDERSIDE OF DECK ABOVE (AS APPLICABLE), FULLY FIRE SEALED ON BOTH SIDES AND WITH PROTECTED OPENINGS AS REQ'D. FIRE/SMOKE COMBINATION DAMPERS MUST BE ADDED, OR RELOCATED, AT ANY NEW POINT OF DUCTWORK'S RATED PENETRATIONS & AS ACCEPTABLE TO INSPECTORS.
4. SAFETY GLAZING REQUIRED ON SIDELITE.
5. MEMBRANE PENETRATION SHALL NOT REDUCE THE FIRE RESISTANCE RATING OF THE 1-HOUR FIRE RATED DEMISING WALL.
6. ALL MATERIALS SHALL BE NONCOMBUSTIBLE DUE TO TYPE II-B CONSTRUCTION.
7. NO WORK IS ALLOWED TO BE ADDED TO, OR MODIFIED FROM, WHAT SHOWN IN PERMIT SET, UNLESS FOLLOW-UP REVISIONS ARE SUBMITTED AND APPROVED AS REQ'D.
8. ACCEPTABILITY OF USE, LAYOUT AND TYPE OF CONSTR'N OF NEWLY CREATED SPACES (NOT IDENTIFIED ON PLANS) SUBJECT TO INSPECTOR'S VERIFICATION & APPROVALS.
9. SUBJECT TO ADDITIONAL REQUIREMENTS FROM M.E.P. REVIEWS, FIRE MARSHAL AND FIELD INSPECTIONS.