1542 SQ FT, CIFO / SIGNATURE DENTAL
5/30/2007 12:00:00 AM
PLAN REVIEW COMMENTS;
1. PHYSICIST REPORT IS REQUIRED BY TRCR FOR PROTECTION AGAINST MACHINE-PRODUCED RADIATION BUT FOR DENTAL OFFICES EQUIPPED WITH MINIMAL-TREAT-RADIATION MACHINES MAY NOT SUBMIT PHYSICIST REPORT AS LONG AS THE DOCTOR IS ASSUMING FULL RESPONSIBILITY FOR TRCR COMPLIANCE AND THE SAFETY OF THE EQUIPMENT IS DOCUMENTED WITH SUBMITTED MANUFACTURER'S CATALOG INFORMATION. PRIOR TO ISSUANCE OF PERMIT MANUFACTURER'S CATALOG INFORMATION SHALL BE SUBMITTED TO THE CITY OF FRISCO.
2. DEMISING WALL BETWEEN TENANTS SPACES SHALL BE CONSTRUCTED WITH AT LEAST 1-HOUR FIRE RESISTIVE CONSTRUCTION FROM FLOOR TO ROOF DECK ABOVE.
3. RESTROOMS FLOORS AND WALLS SHALL HAVE A SMOOTH, HARD, AND NON-ABSORBENT SURFACE, GYPSUM BOARD AND PAINT ARE NOT ALLOWED.
4. DOORS 001 AND 002 SHALL HAVE SAFETY GLAZING.
5. MECHANICAL ROOM 018 SHALL BE SEPARATED FROM THE REST OF THE BUILDING BY ATLEAST 1-HOUR FIRE RATED WALL CONSTRUCTION AND DOOR 008 SHALL HAVE 45 MINUTES FIRE PROTECTION RATING.
6. MEMBRANE PENETRATIONS SHALL NOT REDUCED THE FIRE RESISTANCE RATING OF 1-HOUR FIRE RATED DEMISING WALL.
7. ANY WOODS USED IN A TYPE II-B CONSTRUCTION SHALL BE OF NONCOMBUSTIBLE MATERIAL OR FIRE RETARDANT TREATED WOOD
8. RECEPTIONS DESK MUST BE ADA COMPLIANT.
9. EXHAUST FAN SHALL BE DISCHARGED INTO THE OUTSIDE OF THE BUILDING
10. COMBINATION FIRE/SMOKE DAMPER REQUIRED ON ALL DUCTS AND AIR TRANSFER OPENINGS THAT PENETRATES A RATED CONSTRUCTION.
11. MOPSINK REQUIRED.
12. SUBJECT TO FIELD INSPECTION AND TESTING.