Notes:
6000 SQ FT, CIFO / BRIDES BY DEMETRIOS
3/21/2007 12:00:00 AM
1. vestibule req'd. IECC 2003 802.3.6
2. must post max. occupancy sign for assembly group of 170 IBC 2003 section 1004.3
3. demising wall U UL 465--fire caulk floor to deck
4. all work subject to field approved testing and inspections.
5. mullion connections @ storefront shall be 1 hr. connection both sides.
5a. fully sprinkled.
6. 45 minute doors at storage room, doors shall open out, bad design with storage door opening toward restroom------install fire rated glass for visibility for handicap.
7. storage room/ sales area separation shall be 1 hr. with f/s dampers applicable, see detail sheet.
8. section 1013.4.1 min. egress width 36".
9. section 1020 44" min. width passageway exiting where over 50 occupants
10. TAS 4.15.5 30"x 48" clear floor space in front of LO drinking fountain (no obstructions)